Standard features Engine details
4-cylinder diesel engine
Brush type AC alternator
Bi-directionally optimized mounting system with 4-
point vibration isolation
Cross-flow radiator
Full flow lube oil filter
Fuel filter/water separator
Vertically mounted fuel and oil filters
Replaceable element air cleaner
Remote mountable DC control box
4-position exhaust elbow
30 A battery charging DC alternator
Lifting bracket
Glow plugs for easy starting
Base pan for drip control
Electric fuel pump
Model: Kubota V1505
Design: 4-cycle, liquid-cooled diesel engine
Cylinders: 4, inline vertical
Bore: 3.07 in (78.0 mm)
Stroke: 3.08 in (78.4 mm)
Displacement: 91.4 in
3
(1498 cm
3
)
Compression ratio: 24:1
Lube oil capacity: 7.08 qt (6.7 L)
Power (max): At 1800 r/min: 22.3 hp
Cooling system capacity: 1.25 Gal (4.73 L)
Starting system: Remote, 12 V
Fuel injection pump: Bosch MD mini
Fuel pump: Electric
Combustion chamber: Spherical
Typical fuel consumption
No. 2 diesel fuel, Gal/hr (L/hr)
No load
Half load Full load
10HDKAG
0.29 (1.10) 0.55 (2.08) 1.04 (3.90)
8HDKAG
0.26 (0.98) 0.45 (1.71) 0.94 (3.52)
Alternator details
Design: Cummins Onan, brush type, drip proof
construction
Insulation system: Class F, per NEMA MGI-1.65
and BS 2757; insulating varnish conforms to MIL-I-
24092, grade CB, Class 155 C
Three-phase models: Broad range reconnectable
design for installed voltage flexibility
Exciter system: Electronic voltage regulation
Bearing: Double sealed, pre-lubricated ball bearing.
Cooling: Direct drive centrifugal blower
Damper bar system: Generator set design (100 V
spec unit only) incorporates a damper bar system which
results in low harmonic waveform distortion. This design
feature becomes significant when powering SCR type
loads (converters, etc.)
Generator set details
Control
- Unit mounted, drip-proof, vibration isolated console
DC controls, 12 V system
- Start/stop/preheat switch
- Remote connector for start/stop/preheat switch and
gauge package
- Manual reset fault relay indicating engine shutdown for
high coolant temperature, low oil pressure
- Hour meter
AC controls
- Electronic voltage regulator
- Three-phase models, factory shipped reconnectable (no
breaker on 50 Hz models)
- Three-phase breaker kits available for field fitted
installation
No load/full load
Constant load
Voltage regulation:
±2.5% ±1%
Frequency regulation:
±2.5% ±1%