Product Manual
5-1
5. Specifications
MODEL:
HDKCA HDKCB
GENSET CONTROL: Integrated Microprocessor-Based Engine and Generator Controller
GENERATOR: Single-Bearing, 4-Pole Rotating Field, 1800 RPM
Power (@1.0 power factor) 10,000 W 12,500 W
Voltage 120 / 240 120 / 240
Frequency 60 Hz 60 Hz
Number of Phases 1 1
Current 41.7 amps per leg 52.1 amps per leg
Line Circuit Breaker 2-pole, 45 amp 2-pole, 50 amp
FUEL CONSUMPTION:
No-load
Half-load
Full-load
0.11 gph (0.4 lph)
0.48 gph (1.8 lph)
1.01 gph (3.8 lph)
0.11 gph (0.4 lph)
0.48 gph (1.8 lph)
1.2 gph (4.5 lph)
ENGINE: 3-Cylinder In-Line, Water-Cooled, Indirect-Injection (IDI), 4-Stroke Cycle Diesel
Bore 3.43 in (87 mm)
Stroke 3.64 in (92.4 mm)
Displacement 100.5 in
3
(1,647 cc)
Compression Ratio 22.6 : 1
Fuel Injection Timing (BTDC) 14.5°
Firing Order 1−3−2
Fuel Nozzle Injection Pressure 1991 psi (13.731 mPa)
Cylinder Compression Test 370 psi (2.55 mPa) minimum
Valve Lash: Intake & Exhaust (cold)
0.0071 to 0.0087 in (0.18 to 0.22 mm)
Oil Capacity (with filter)
5.9 quart (5.6 liter)
Cooling System Capacity
6.6 quart (6.2 liter)
DC SYSTEM:
Nominal Battery Voltage
12 volts
Minimum Battery Capacity
CCA (Cold Cranking Amps)
475 amps down to 0° F (−17° C)
650 amps down to −20° F (−29° C)
Battery Recharging
Installer must provide for battery charging
WEIGHT: 775 lbs (351 kg) 794lbs (360 kg)
SIZE (L x W x H): 41.4 x 24.5 x 27 in (105 x 62 x 68.6 cm)
SOUND LEVEL: 68 dB(A) @ 10 ft (3m) & 54 dB(A) @ 50 ft (15m)—in “free field site” @ half load