Specifications
To bypass, turn the blue knob clockwise (see directional arrow on end of
knob) until the knob stops as shown. DO NOT OVERTIGHTEN! (Figure 12a).
To return to service, turn the blue knob counter-clockwise (see directional
arrow on the end of knob) until the knob stops as shown. DO NOT
OVERTIGHTEN! (Figure 12b)
Drain Line Connection
Refer to Figure 8 and Table 2 & 3, under the applicable tank size for drain line
length and height limitations.
• Remove 1/2” pipe clamp from end of drain elbow.
• Route a length of 1/2” drain line from the drain elbow to the drain.
• Fasten the drain line to the elbow with the clamp.
• Secure the drain line to the drain to prevent its movement during
regeneration. A loop in the end of the tube will keep it lled with water
and will reduce splashing at the beginning of each regeneration
Average Water
Pressure psi
Height of Drain Discharge Above Floor on Which Filter Sets
4” 1 ft. 2 ft. 3 ft. 4 ft. 5 ft. 6 ft. 7 ft. 8 ft. 9 ft. 10 ft.
30 56 50 40 30 20 10
50 112 106 96 86 76 66 56 46 36 26 16
70 143 137 127 117 107 97 87 77 67 57 47
90 153 147 137 127 117 107 97 87 77 67 57
120 159 153 143 133 123 113 103 93 83 73 63
Table 2 - Culligan
®
Automatic Water Filters, 8 Inch
Average Water
Pressure psi
Height of Drain Discharge Above Floor on Which Filter Sets
4” 1 ft. 2 ft.
3 ft. 4 ft. 5 ft.
6 ft. 7 ft. 8 ft. 9 ft.
10 ft.
30 44 38 28 18
50 103 97 87 77 67 57 47 37 27 17 7
70 129 123 113 103 93 83 73 63 53 43 33
90 145 139 129 119 109 99 89 79 69 59 49
120 153 147 137 127 117 107 97 87 77 67 57
Table 3 - Culligan
®
Automatic Water Filters, 10 Inch
Electrical Connections
The power cord needs to be connected to the plug-in transformer, wire orientation is not
critical. Figure 13 shows the cord attachment to the transformer.
13 Culligan Medallist Series
®
Figure 13
Note: Observe all state and local electrical codes.
Note: The plug-in transformer is rated for indoor installations only.
Figure 12a
Note: Waste connections or drain outlets shall be designed and
constructed to provide for connection to the sanitary waste system through
an air gap of 2 pipe diameters or 1 inch, whichever is larger.
Note: Observe all plumbing codes. Most codes require an anti-siphon
device or air gap at the discharge point. The system and installation must
comply with state and local laws and regulations.
About 1-1/4”
A screwdriver shank may be
used in the slot as a lever for
extra turning force if needed.
Figure 12b