The product includes current limiting circuitry for 
protection at continuous overload. The default setting for 
the product is hic-up mode if the maximum output current 
is exceeded and the output voltage is below 0.3×V
out
, set 
in command IOUT_OC_LV_FAULT_LIMIT (0x48). Above 
the trip voltage value in command 0x48 the product will 
continue operate while maintaining the output current at 
the value set by IOUT_OC_FAULT_LIMIT (0x46). The load 
distribution should be designed for the maximum output 
short circuit current specied. 
Droop Load Share variants (DLS) will enter hic-up mode, 
with a trip voltage, 0.04×V
out
, set in command IOUT_
OC_LV_FAULT_LIMIT (0x48). Above the trip voltage in 
command (0x48) the product will continue operate while 
maintaining the output current at the value set by IOUT_
OC_FAULT_LIMIT (0x46). 
The over current protection of the product can be 
recongured using the PMBus interface.
Over Current Protection (OCP)
The input of the product can be protected from high input 
voltage and low input voltage. The over/under-voltage 
fault level and fault response can be congured via the 
PMBus interface.
Input Over/Under voltage protection
The product has a Pre-bias start up functionality and will 
not sink current during start up if a Pre-bias source is 
present at the output terminals. If the Pre-bias voltage 
is lower than the target value set in VOUT_COMMAND 
(0x21), the product will ramp up to the target value. If 
the Pre-bias voltage is higher than the target value set in 
VOUT_COMMAND (0x21), the product will ramp down to 
the target value and in this case sink current for a limited 
of time set in the command TOFF_MAX_WARN_LIMIT 
(0x66).
Pre-bias Start-up Capability
The product provides Power Good (PG) ag in the Status 
Word register that indicates the output voltage is within a 
specied tolerance of its target level and no fault condition 
exists. If specied in section Connections, the product 
also provides a PG signal output. The Power Good signal 
is by default congured as active low, Push-pull and can 
be re-congured via the PMBus interface. The Power Good 
output can be congured as Push-pull or “High Z when 
active” to permit AND’ing of parallel devices. It is not 
recommended to use Push-pull when paralleling PG-pins, 
see MFR_MULTI_PIN_CONFIG.
Power Good 
This product does not support synchronization, tracking or 
external reference.
Synchronization, Tracking and External reference
The switching frequency is set to 140 kHz as default but 
this can be recongured via the PMBus interface. The 
product is optimized at this frequency but can run at 
lower and higher frequency, (125-150 kHz). The electrical 
performance can be affected if the switching frequency is 
changed.
Switching frequency adjust using PMBus
The MFR_MULTI_PIN_CONFIG (0xF9) command enables 
or disables different functions inside the product. This 
command can be congured according to the table for 
different functions.
MFR_MULTI_PIN_CONFIG
Bit 7:6 
00 = Stand alone 
01 = Slave (N/A) 
10 = DLS 
11 = Master (N/A) 
1  1  1  1  1  1  0  0  0  0  0  0 
0  0  0  0  0  0  0  0  0  0  0  0 
Bit 5 
Power Good High Z 
when active 
0  0  0  0  1  1  0  0  0  0  1  1 
Bit 4 
Tracking enable 
(N/A) 
0  0  0  0  0  0  0  0  0  0  0  0 
Bit 3 
External reference 
(N/A) 
0  0  0  0  0  0  0  0  0  0  0  0 
Bit 2 
Power Good 
Enable 
0  0  1  1  1  1  0  0  1  1  1  1 
Bit 1 
Reserved 
1  1  1  1  1  1  0  0  0  0  0  0 
Bit 0 
Secondary Remote 
Control Pull 
up/down resistor 
enable 1) 
0  1  0  1  0  1  0  1  0  1  0  1 
1) When not used 
with PMBus, the 
CTRL input can be 
internally pulled up 
or down depending 
on if it is active high 
or low. When active 
low it will be pulled 
up and vice versa 
DLS, PMBus Control (0x82) 
DLS, Sec RC w
/
 pull up/down (0x83) 
DLS, Power Good Push-pull, PMBus Control 
(0x86) 
DLS, Power Good Push-pull,  
Sec RC w/ pull up/down (0x87) 
DLS, Power Good High Z when active, 
PMBus Control (0xA6) 
DLS, Power Good High Z when active, 
Sec RC w/ pull up/down (0xA7) 
Stand alone, PMBus Control (0x00) 
Stand alone, Sec RC w/ pull up/down (0x01) 
Stand alone, Power Good Push-pull, PMBus 
Control (0x04) 
Stand alone, Power Good Push-pull,  
Sec RC w/ pull up/down (0x05) 
Stand alone, Power Good High Z when 
active, PMBus Control (0x24) 
Stand alone, Power Good High Z when 
active, Sec RC w/ pull up/down (0x25) 
The MFR_MULTI_PIN_CONFIG can be recongured using 
the PMBus interface. Default conguration is set to Power 
Good Push-Pull (0x04) for stand alone variants and DLS 
Power Good Push-Pull (0x86) for Droop Load Share 
variants.
This product has two data storage set: Default data (CUI 
factory) and User data. The User data set’s priority is 
higher than the Default data. The User data area is empty 
while shipped to customer. After boot-up, if the controller 
found no data stored in User data area, it will load Default 
data instead.
Customer can change the RAM data and store the changes 
into ash memory by PMBUS Store_User_All, next power 
cycle will load the User data into RAM for execute.
Store_Default_All is write protected to ensure the factory 
settings is always available for recovery.
User customized settings
For more information, please visit the product page.