When exhausting the refrigerant, ex-
haust it to the low pressure side slowly
and check the pressure graduation
and sight glass to check the amount
of refrigerant.
Pay attention to the contamination of
radiator.
2. Excess of refrigerant charging
Status: Not cool
Phenomena:
- Pressure rising by overcharging of refrigerant
- Lack of cooling of the compressor
Cause:
- Pressure rising by overcharging of refrigerant
- Lack of cooling of the compressor
Action:
- Clean the compressor
- Check and adjust fan belt or compressor motor
- Check the amount of refrigerant
3. Air mixing (lack of vacuum working)
Status: Not cool
Phenomena:
- The pressure of high /low pressure side is high.
- The pipe of low pressure side is not cold.
Cause: Air mixing in the refrigerating cycle. In case
of no vacuum working, the graduation is shown on
the left figure.
Action: When charging the refrigerant by making a
vacuum, check the guide.
In case of operating for a long time in the state of air
mixing, replace the receiver drier.
2.5 ~ 3.5 kgf/cm
2
35.6 ~ 49.8 psi
20 kgf/cm
2
284.5 psi
Low excess of
refrigerant charging
High excess of
refrigerant charging
2.5 ~ 3.5 kgf/cm
2
35.6 ~ 49.8 psi
23 ~ 24 kgf/cm
2
327.1 ~ 341.3 psi
Low air mixing in the
refrigerating cycle
High air mixing in the
refrigerating cycle