nxp/c frequency converters user's manual
vacon • 1 AT LEAST THE FOLLOWING STEPS OF THE START-UP QUICK GUIDE MUST BE PERFORMED DURING THE INSTALLATION AND COMMISSIONING. IF ANY PROBLEMS OCCUR, PLEASE CONTACT YOUR LOCAL DISTRIBUTOR. Start-up Quick Guide 1. Check that the delivery corresponds to your order, see Chapter 3. 2. Before taking any commissioning actions read carefully the safety instructions in Chapter 1. 3. Before the mechanical installation, check the minimum clearances around the unit (Chapter 5.
2 • vacon CONTENTS VACON NXC USER’S MANUAL INDEX 1 SAFETY 2 INTRODUCTION 3 RECEIPT OF DELIVERY 4 TECHNICAL DATA 5 MOUNTING 6 CABLING AND CONNECTIONS 7 LOW HARMONIC REGENERATIVE CABINET DRIVE 8 INSTALLATION INSTRUCTIONS 9 CONTROL KEYPAD 10 COMMISSIONING 11 FAULT TRACING Tel.
vacon • 3 INDEX Document code: ud01011.doc Date: 8.1.2009 1. 1.1 1.2 1.3 1.4 SAFETY............................................................................................................................................ 5 Warnings ............................................................................................................................................ 5 Safety instructions...............................................................................................................
4 • vacon 6.2.2 6.2.3 6.2.4 6.2.5 6.2.6 6.2.7 Mains and motor cables.............................................................................................................. 33 Thermal supervision of option +ODU ......................................................................................... 42 DC supply and brake resistor cables ......................................................................................... 42 Control cable ..........................................................
SAFETY 1. vacon • 5 SAFETY ONLY A COMPETENT ELECTRICIAN MAY CARRY OUT THE ELECTRICAL INSTALLATION 1.1 Warnings 1 2 3 4 5 6 7 8 9 1.2 The Vacon NX frequency converter is meant for fixed installations only. Do not perform any measurements when the frequency converter is connected to the mains. Do not perform any voltage withstand tests on any part of Vacon NX. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damaged product.
6 • vacon 1.3 SAFETY Earthing and earth fault protection The Vacon NX frequency converter must always be earthed with an earthing conductor connected to the PE bar in the lower front side of the cabinet. The earth fault protection inside the frequency converter protects only the converter itself against earth faults in the motor or the motor cable. It is not intended for personal safety.
INTRODUCTION 2. vacon • 7 INTRODUCTION The Vacon NXC is a product range of free standing enclosed frequency converters for the high power range. The NXC is a modular product intended for use in all applications where reliability and high availability is appreciated. This manual gives the basic information required to successfully perform installation and basic commissioning. Due to the high amount of options available, not all possible variations are described in this manual.
8 • vacon 2.1 INTRODUCTION Manufacturer's declaration of conformity Below you can find the Manufacturer's Declarations of Conformity assuring the compliance of Vacon NXP/C frequency converters with the EMC-directives. EU DECLARATION OF CONFORMITY We Manufacturer's name: Vacon Oyj Manufacturer's address: P.O.Box 25 Runsorintie 7 FIN-65381 Vaasa Finland hereby declare that the product Product name: Vacon NXP/C Frequency converter Model designation: Vacon NXP/C 0261 5…. to 2700 5….
RECEIPT OF DELIVERY 3. vacon • 9 RECEIPT OF DELIVERY Vacon NX frequency converters have undergone scrupulous tests and quality checks at the factory before they are delivered to the customer. However, after unpacking the product, check that no signs of transport damages are to be found on the product and that the delivery is complete (compare the type designation of the product to the code below).
10 • vacon 3.2 RECEIPT OF DELIVERY NXC additional option codes The NXC enclosure solution contains additional pre-engineered hardware options. These options are appended to the basic type code by using “+” codes. You will find the complete type code on the name plate of the unit. The most common NXC options are listed below: 3.2.1 Cabling (C-group) +CIT Input (mains) cabling from TOP +COT Output motor cabling from TOP 3.2.
RECEIPT OF DELIVERY 3.2.8 Auxiliary Equipment (A-group) +AMF Motor fan control +AMH Motor heater feeder +AMB Mechanical brake control +ACH Cabinet heater +ACL Cabinet light +ACR Control relay +AAI Analogue signal isolator +AAC Aux. contact (input device) +AAA Aux. contact (control voltage devices) +ATx Aux. Transformer 400-690/230VAC +ADC Power supply 24VDC 10A +ACS 230VAC customer socket 3.2.
12 • vacon 3.3 RECEIPT OF DELIVERY Storage If the frequency converter is to be kept in store before use make sure that the ambient conditions are acceptable: Storing temperature Relative humidity –40…+70 C <95%, no condensation The environment should also be free from dust. If there is dust in the air the converter should be well protected to make sure dust does not get into the converter.
RECEIPT OF DELIVERY 3.5 vacon • 13 Warranty Only manufacturing defects are covered by the warranty. The manufacturer assumes no responsibility for damages caused during or resulting from transport, receipt of the delivery, installation, commissioning or use.
14 • vacon TECHNICAL DATA 4. TECHNICAL DATA 4.1 Power ratings 4.1.1 Vacon NXP/C – Mains voltage 380—500 V High overload = Max current IS, 2 sec/20 sec, Rated overload current, 1 min/10 min Following continuous operation at rated output current, rated overload current for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.
TECHNICAL DATA 4.1.2 vacon • 15 Vacon NXC Regenerative low harmonic drives – Mains voltage 380—500 V High overload = Max current IS, 2 sec/20 sec, Rated overload current, 1 min/10 min Following continuous operation at rated output current, rated overload current for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.
16 • vacon 4.1.3 TECHNICAL DATA Vacon NXP/C 6 – Mains voltage 500—690 V High overload = Max current IS, 2 sec/20 sec, Rated overload current, 1 min/10 min Following continuous operation at rated output current, rated overload current for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.
TECHNICAL DATA 4.1.4 vacon • 17 Vacon NXC Regenerative low harmonic drives – Mains voltage 525—690 V High overload = Max current IS, 2 sec/20 sec, Rated overload current, 1 min/10 min Following continuous operation at rated output current, rated overload current for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.
18 • vacon 4.2 TECHNICAL DATA Technical data Mains connection Motor connection Control characteristics Input voltage Uin Input frequency Connection to mains 380…500V; 500…690V; –10%…+10% 380...500V;525...690V; –10%…+10% (regenerative drives) 45…66 Hz Once per minute or less (normal case); Output voltage Continuous output current 0—Uin Ambient temperature max. +40°C See Table 4-1 and Table 4-3. Overloadability High: 1.5 x IH (1 min/10 min), Low: 1.
TECHNICAL DATA EMC (at default settings) vacon • 19 Immunity Emissions Safety Control connections (factory default I/O) Analogue input voltage Analogue input current Digital inputs (6) Auxiliary voltage Output reference voltage Analogue output Digital outputs Relay outputs Protections Thermistor input (OPTA3) Overvoltage trip limit Undervoltage trip limit Earth fault protection Mains supervision Motor phase supervision Overcurrent protection Unit overtemperature protection Motor overload protection
20 • vacon 5. MOUNTING 5.1 Dimensions MOUNTING The table below shows the dimensional drawing of the basic cabinet. Please note that certain NXC options will further affect the total width or height of the cabinet. Always refer to the delivery specific information for the exact dimensions. W1 H1 D1 Figure 5-1.
MOUNTING Type vacon • 21 Dimensions [mm] IP21 W1 H1 D1 Dimensions [mm] IP54 W1 H1 D1 0385—0520 5 606** 2275* 605 606** 0261—0416 6 0590—0730 5 806** 2275* 605 806** 0460—0590 6 0820—1030 5 1206** 2275* 605 1206** 0650—0820 6 1150 5 1406** 2275* 605 1406** 0920—1180 6 1300—1450 5 2006** 2275* 605 2006** 1770—2150 5 2806** 2275* 605 2806** 1500—2250 6 Table 5-2.
22 • vacon 5.2 MOUNTING Lifting the unit out of the transport packaging The unit is delivered either in a wooden box or a wooden cage. The box may be transported either horizontally or vertically, while transportation of the cage in a horizontal position is not allowed. Always refer to shipping marks for more detailed information. To lift the unit out of the box, use lifting equipment capable of handling the weight of the cabinet.
MOUNTING 5.3.1 vacon • 23 Fixing to the floor and to the wall In installations where the cabinet is mounted against the wall, it is more convenient to fix the top of the cabinet to the wall. Fix the cabinet in the two front corners to the floor with bolts. Fix the top part to the wall with bolts. Note that the rails and the fixing lugs can be moved horizontally to make sure the cabinet stands in a horizontal position.
24 • vacon 5.4 MOUNTING AC choke connections Note: The NXC regenerative low-harmonic drive incorporates an LCL filter instead of AC chokes and this instruction can be ignored. The AC input choke carries out several functions in the Vacon NX 6- and 12-pulse frequency converter. The input choke is needed as an essential component for motor control, to protect the input and DC-link components against abrupt changes of current and voltage as well as to function as a protection against harmonics.
MOUNTING 5.5 vacon • 25 Auxiliary voltage transformer tappings Note: An auxiliary voltage transformer is always included as standard in NXC regenerative lowharmonic drives. If the drive is ordered with an auxiliary voltage transformer for 230V auxiliary voltage supply (+ATx option) the tappings of the transformer have to be set according to the mains voltage. The tappings of the transformer in 500V drives is by default set to 400V and in 690V drives to 690V unless otherwise ordered.
26 • vacon 5.6 5.6.1 MOUNTING Cooling Free space around the cabinet Enough space must be left above and in front of the cabinet to ensure sufficient cooling and space for maintenance. The amount of cooling air required is indicated in the table below. Also make sure that the temperature of the cooling air does not exceed the maximum ambient temperature of the converter. 200 mm 800 mm Figure 5-7.
MOUNTING vacon • 27 Type Cooling air required [m3/h) 0261—0520 5 3100 0125—0416 6 0590—1030 5 6200 0460—0820 6 1150—1450 5 7700 0920—1180 6 1770—2700 5 15400 1500—2250 6 Table 5-5. Required cooling air for NXC regenerative low-harmonic drives 24-hour support: +358 (0)40 837 1150 • Email: vacon@vacon.
28 • vacon 5.7 MOUNTING Power losses The power loss of the frequency converter varies greatly with load and output frequency as well as with the switching frequency used. For dimensioning of cooling or ventilation equipment for electrical rooms the following generic formula gives a good approximation of the heat losses at nominal conditions: Ploss [kw] = Pmot [kW] x 0,025 5 Tel.
CABLING AND CONNECTIONS vacon • 29 6. CABLING AND CONNECTIONS 6.1 Understanding the power unit topology Figure 6-1 and Figure 6-2 show the principles for mains and motor connections of the basic 6-pulse drive in frame sizes FR10 to FR14. Some units built in frame size FR11 have double input devices and require an even number of supply cables but an uneven number of motor cables can be used.
30 • vacon CABLING AND CONNECTIONS FI9-10 FI12 Single input Single input AFE INU Single output M AFE AFE INU INU Single output M FI14 FI13 Single input Double input AFE AFE AFE INU INU INU du/dt du/dt Single output Double output M M ud1 011k1 7.fh11 Figure 6-2.
CABLING AND CONNECTIONS 6.2 vacon • 31 Power connections 6.2.1 LCL filter wiring diagram of NXC regenerative low-harmonic drive The LCL filter in the NXC regenerative low-harmonic drive contains a choke on the mains side, capacitors and a choke on the AFE side. The LCL filter also includes capacitors connected against ground potential. There are resistors connected across the capacitors for discharging these when the LCL filter is disconnected from the input power. Figure 6-3.
32 • vacon CABLING AND CONNECTIONS Remove Remove Remove Remove Figure 6-4. HF capacitors in NXC regenerative low-harmonic drive mechanical sizes Fi9,Fi10 and Fi12 LCL filter. Remove Remove Remove Remove Figure 6-5. HF capacitors in NXC regenerative low-harmonic drive mechanical sizes Fi13-Fi14 LCL filter. 6 Tel.
CABLING AND CONNECTIONS 6.2.2 vacon • 33 Mains and motor cables The mains cables are connected to terminals L1, L2 and L3 (12-pulse units 1L1, 1L2, 1L3, 2L1, 2L2, 2L3) and the motor cables to terminals marked with U, V and W, see Figure 6-7. In converters consisting of double input sections, an even number of input cables is required. In converters consisting of double power modules an even number of motor cables is needed. See tables 6-2 to 6-6 for cabling recommendations.
34 • vacon CABLING AND CONNECTIONS Use cables with a temperature rating of at least +70 C. As a rule of thumb, cables and the fuses can be dimensioned according to the frequency converter nominal OUTPUT current which you can find on the rating plate. Dimensioning according to the output current is recommended because the frequency converter input current never significantly exceeds the output current. Tables 6-2 and show the minimum dimensions of Cu- and Al-cables and the recommended aR fuse sizes.
CABLING AND CONNECTIONS Connect mains cables to terminals L1, L2 and L3 on the input device (if used) or to power terminals on the converter using cable lugs vacon • 35 Conn ect motor cables to terminals U, V and W on converter using cable lugs Strip 2 Strip 1 PE Connect the PE conductor to the PE bar EMC-earthing clamp for motor cable screen Figure 6-7. Routing of power cables, 6- and 12-pulse drives, bottom cabling, frames FR10-FR12 (FR10 +ILS as example).
36 • vacon CABLING AND CONNECTIONS Connect mains cables to terminals L1, L2 and L3 (behind the plexiglass) on the converter Connect motor cables to terminals U, V and W on converter Connect the PE conductors to the PE bar Connect the PE conductors to the PE bar Figure 6-9.
CABLING AND CONNECTIONS vacon • 37 Connect motor cables to terminals U, V and W on converter Connect mains cables to terminals L1, L2 and L3 on the AC drive Connect the PE conductor to the PE bar Figure 6-11. Routing of power cables, bottom cabling, frame Fi12 +ODU (optional) Connect motor cables to terminals U, V and W on converter Connect mains cables to terminals L1, L2 and L3 (behind the plexiglass) on the converter Figure 6-12.
38 • vacon CABLING AND CONNECTIONS Figure 6-13. Routing of power cables, bottom cabling, frame Fi14 6.2.2.1 Routing of power cables through bottom of cabinet Route the supply and motor cables through the cabinet bottom as shown in Figure 6-14. To conform to the EMC requirements, a particular cable gland shall be used. The cable glands are designed to be used together with screened cables when electromagnetic compatibility (EMC) is required. Figure 6-14. Routing of supply and power cables 6 Tel.
CABLING AND CONNECTIONS vacon • 39 Cable tie Fastening spring Metal sock PE(N) screen Assembly plate Cable Bush ring Rubber sealing ud1011k11.fh11 Figure 6-15. Components of the cable gland set Installing the cable gland Unless the cable gland is already installed by the manufacturer, follow the procedure below to do this: 1. 2. 3. 4. Assemble the rubber sealing in the narrow groove of the bush ring. Make sure that the gap between the assembly plate and the sealing is tight.
40 • vacon 6 CABLING AND CONNECTIONS Tel.
CABLING AND CONNECTIONS 6.2.2.2 vacon • 41 Installation of ferrite rings (+OCM) on the motor cable Modern PWM Frequency converters based on IGBT transistors generate output pulses having short rise times (0,1...0,2 µs). Those pulse edges increase the stress for motor insulation and also generate high frequency common mode voltages on the motor output. Common mode voltage increases emitted radio interferences and might cause danger of bearing currents when larger motor frames (> 100kW) are used.
42 • vacon 6.2.3 CABLING AND CONNECTIONS Thermal supervision of option +ODU Option +ODU can also be equipped with a thermal supervision which will indicate if the filter temperature has exceeded safe limits. Always refer to cabinet specific electrical drawings for details.This NC contact is wired to the external fault input DIN3 by factory default. NOTE! If the external fault input DIN3 is used for other purposes, make sure that the +ODU fan supervision wiring is changed accordingly.
CABLING AND CONNECTIONS 6.2.6 vacon • 43 Cable and fuse sizes, 380-500V units The table below shows typical cable sizes and types that can be used with the converter. The final selection should be made according to local regulations, cable installation conditions and cable specification. 6.2.6.
44 • vacon 6.2.6.
CABLING AND CONNECTIONS 6.2.6.
46 • vacon 6.2.7 CABLING AND CONNECTIONS Cable and fuse sizes, 500/525-690V units The table below shows typical cable sizes and types that can be used with the converter. The final selection should be done according to local regulations, cable installation conditions and cable specification. 6.2.7.
CABLING AND CONNECTIONS 6.2.7.
48 • vacon 6.2.7.
LOW HARMONIC REGENERATIVE CABINET DRIVE 7. vacon • 49 LOW HARMONIC REGENERATIVE CABINET DRIVE This chapter describes the functionalities of control devices (switches, push-buttons and LED lamps) of the NXC low-harmonic regenerative drive (mechanical units FI9-14). The functionalities of additional “+” options are not described here. 7.
50 • vacon LOW HARMONIC REGENERATIVE CABINET DRIVE Turning the switch –S10 into position 0 will open the circuit-breaker if it is closed or stop the possible ongoing pre-charging regardless of the selected control place/manner. Turning the switch into position 1 enables the pre-charging and the circuit-breaker to be controlled by the selected mode of the REM-MAN-AUTO selector switch. Turning the switch into position Start will start the pre-charging of DC busbar.
LOW HARMONIC REGENERATIVE CABINET DRIVE vacon • 51 Figure 7-4. Circuit diagram of remote contacts for the control of the MCCB and pre-charging circuit (NXC regenerative low-harmonic FR12) In case of a voltage drop of <0.7xUN or a blackout in the supplying network, the undervoltage release coil will open the circuit-breaker and pre-charging and MCCB closing has to be activated by the remote charging pulse when the supply is energized. 7.1.
52 • vacon LOW HARMONIC REGENERATIVE CABINET DRIVE In case of an overcurrent situation the fault that caused the circuit-breaker to trip should be identified and removed before the circuit-breakers can be reset. The MCCB can only be reset by pressing the push button -S6 when the –S11 REM-MAN-AUTO switch is in MAN position. Figure 7-6. MCCB Reset push-button (-S11) This will reset the circuit-breaker and, at the same time in FR9, FR10 or FR12 solution, recharge the spring system of the motor operators.
INSTALLATION INSTRUCTIONS 8. vacon • 53 INSTALLATION INSTRUCTIONS 1 2 3 4 Before starting the installation, check that none of the components of the frequency converter is live. Make sure that the space where the converter is installed, and the converter itself, is clean and free from particles, dust or humidity that could harm the converter when it is powered on.
54 • vacon INSTALLATION INSTRUCTIONS 6 7 8.1 Connect the cables: Strip the motor and mains cables Remove the protection grids for the input terminals and the protection covers on the converter module(s). Pull the cable through the bottom plate and fix the PE conductor to the PE bar of the cabinet. Connect the mains, motor and control cables into their respective terminals. Use cable lugs on the power cables. In units with parallel cables (FR11 and FR12) make sure the cabling is fully symmetrical.
INSTALLATION INSTRUCTIONS 8.1.1 vacon • 55 Cable and motor insulation checks 1. Motor cable insulation checks Disconnect the motor cable from terminals U, V and W of the frequency converter and from the motor. Measure the insulation resistance of the motor cable between each phase conductor as well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1M . 2.
56 • vacon 8.2 INSTALLATION INSTRUCTIONS Control unit The control unit of the frequency converter consists roughly of the control board and additional boards (see Figure 8-1 and Figure 8-2) connected to the five slot connectors (A to E) of the control board. The control board is connected to the power unit through a D-connector (1) or fibre optic cables. A Figure 8-1. NX control board B C D E Figure 8-2.
INSTALLATION INSTRUCTIONS 8.2.1 vacon • 57 Control connections The basic control connections for boards A1 and A2/A3 are shown in Chapter 8.2.2. The signal descriptions are presented in the All in One Application Manual. OPT-A2 OPT-A3 Board OPT-A1 Boards OPT-A2 and in slot A OPT-A3 in slot B Figure 8-3.
58 • vacon 8.2.1.1 INSTALLATION INSTRUCTIONS Control cables The control cables shall be at least 0.5 mm2 screened multicore cables, see Table 6-1. The maximum terminal wire size is 2.5 mm2 for the relay terminals and 1.5 mm2 for other terminals. Find the tightening torques of the option board terminals in Table below. Terminal screw Relay and thermistor terminals (screw M3) Other terminals (screw M2.6) Tightening torque Nm lb-in. 0.5 4.5 0.2 1.8 Table 8-2. Tightening torques of terminals 8.2.1.
INSTALLATION INSTRUCTIONS 8.2.2 vacon • 59 Control terminal signals OPT-A1 1 2 Terminal +10 Vref AI1+ Signal Reference voltage Analogue input, voltage or current 3 GND/AI1– Analogue input common 4 AI2+ Analogue input, voltage or current 5 GND/AI2– Analogue input common 6 24 Vout (bidirectional) 24V auxiliary voltage 7 8 9 10 11 GND DIN1 DIN2 DIN3 CMA I/O ground Digital input 1 Digital input 2 Digital input 3 Digital input common A for DIN1, DIN2 and DIN3.
60 • vacon INSTALLATION INSTRUCTIONS OPT-A2 21 22 23 Terminal RO1/1 RO1/2 RO1/3 24 25 26 RO2/1 RO2/2 RO2/3 Signal Relay output 1 Relay output 2 Technical information Switching capacity 24VDC/8A 250VAC/8A 125VDC/0.4A Min.switching load 5V/10mA Switching capacity 24VDC/8A 250VAC/8A 125VDC/0.4A Min.switching load 5V/10mA Table 8-4.
INSTALLATION INSTRUCTIONS 8.2.2.2 vacon • 61 Jumper selections on the OPT-A1 basic board The user is able to customise the functions of the frequency converter to better suit his needs by selecting certain positions for the jumpers on the OPT-A1 board. The positions of the jumpers determine the signal type of analogue and digital inputs. On the A1 basic board, there are four jumper blocks X1, X2, X3 and X6 each containing eight pins and two jumpers.
62 • vacon INSTALLATION INSTRUCTIONS Jum per block X 1 : AI1 m ode A B C D A AI1 mode: 0...20mA; Current input A B C D B C D A B C D Jum per block X 6 : AO1 m ode A B C D AO1 mode: 0...20mA; Current output A B C D D B C D B C D AI2 mode: Voltage input; 0...10V (differential) A AI1 mode: Voltage input; -10...10V C AI2 mode: Voltage input; 0...10V A AI1 mode: Voltage input; 0...10V (differential) B AI2 mode: 0...20mA; Current input A AI1 mode: Voltage input; 0...
INSTALLATION INSTRUCTIONS 8.3 vacon • 63 Connecting power supply and internal control cables You might need to establish the fibre cable connections from the star coupler board to the power module. Connect the cables according to Figure 8-11. The control unit uses 24 VDC supplied from the ASIC board, which is located on the left side of the power unit 1. To access the board, remove the protective cover in front of the power module.
64 • vacon 8.
CONTROL KEYPAD 9. vacon • 65 CONTROL KEYPAD The control keypad is the link between the Vacon frequency converter and the user. The Vacon NX control keypad features an alphanumeric display with seven indicators for the Run status (RUN, , READY, STOP, ALARM, FAULT) and three indicators for the control place (I/O term/ Keypad/BusComm). There are also three Status Indicator LEDs (green - green - red), see Status LEDs (green – green – red) below. The control information, i.e.
66 • vacon 9.1.2 CONTROL KEYPAD Control place indications The symbols I/O term, Keypad and Bus/Comm (see Figure 9-1) indicate the choice of control place made in the Keypad control menu (M3) (see chapter 9.3.3). a I/O term = I/O terminals are the selected control place; i.e. START/STOP commands or reference values etc. are given through the I/O terminals. b Keypad = Control keypad is the selected control place; i.e. the motor can be started or stopped, or its reference values etc.
CONTROL KEYPAD 9.2 vacon • 67 Keypad push-buttons The Vacon alphanumeric control keypad features 9 push-buttons that are used for the control of the frequency converter (and motor), parameter setting and value monitoring. Figure 9-2. Keypad push-buttons 9.2.1 Button descriptions reset = This button is used to reset active faults (see Chapter 9.3.4). select = This button is used to switch between two latest displays.
68 • vacon 9.3 CONTROL KEYPAD Navigation on the control keypad The data on the control keypad are arranged in menus and submenus. The menus are used for example for the display and editing of measurement and control signals, parameter settings (chapter 9.3.2), reference values and fault displays (chapter 9.3.4). Through the menus, you can also adjust the contrast of the display (page 87).
CONTROL KEYPAD vacon • 69 READY R EADY I/Oterm R EADY I/Ote rm Expander boards Parameters A:NXOPTA1 G1 G5 STOP I/Oterm G1 READY STOP I/Oterm P1 P3 G1 R EADY I/Ote rm System Menu Language S1 S9 English READY Browse READY I/Oterm READY I/Ote rm Fault history I/Oterm 11 Output phase H1 H3 STOP Operation days 17 T1 T7 FAULT STOP I/Oterm FAULT STOP I/Ote rm Active faults F0 STOP or: T1 READY ST OP Keypad control T7 17 R EADY Control Place I/O Terminal REA
70 • vacon 9.3.1 CONTROL KEYPAD Monitoring menu (M1) You can enter the Monitoring menu from the Main menu by pushing the Menu button right when the location indication M1 is visible on the first line of the display. How to browse through the monitored values is presented in Figure 9-4. The monitored signals carry the indication V#.# and they are listed in Table 9-1. The values are updated once every 0.3 seconds. This menu is meant only for signal checking. The values cannot be altered here.
CONTROL KEYPAD 9.3.2 vacon • 71 Parameter menu (M2) Parameters are the way of conveying the commands of the user to the frequency converter. The parameter values can be edited by entering the Parameter Menu from the Main Menu when the location indication M2 is visible on the first line of the display. The value editing procedure is presented in Figure 9-5. Push the Menu button right once to move into the Parameter Group Menu (G#).
72 • vacon CONTROL KEYPAD Keypa d Input signals G1 READY G8 READY Ke ypad Ke ypad Parameters Basic parameters P1 P18 G1 G8 READY Min Frequency 13.95 Hz READY Keypad Keypad Min Frequency 13.95 Hz READY Keypad Min Frequency enter 14.45 Hz Figure 9-5. Parameter value change procedure 9 Tel.
CONTROL KEYPAD 9.3.3 vacon • 73 Keypad control menu (M3) In the Keypad Controls Menu, you can choose the control place, edit the frequency reference and change the direction of the motor. Enter the submenu level with the Menu button right. Code Parameter Min Max Unit P3.1 Control place 1 3 R3.2 Keypad reference Par. 2.1.1 Par. 2.1.2 P3.3 Direction (on keypad) 0 R3.
74 • vacon 9.3.3.2 CONTROL KEYPAD Keypad reference The keypad reference submenu (P3.2) displays and allows the operator to edit the frequency reference. The changes will take place immediately. This reference value will not, however, influence the rotation speed of the motor unless the keypad has been selected as source of reference. NOTE: The maximum difference in RUN mode between the output frequency and the keypad reference is 6 Hz.
CONTROL KEYPAD 9.3.4 vacon • 75 Active faults menu (M4) The Active faults menu can be entered from the Main menu by pushing the Menu button right when the location indication M4 is visible on the first line of the keypad display. When a fault brings the frequency converter to a stop, the location indication F1, the fault code, a short description of the fault and the fault type symbol (see Chapter 9.3.4.1) will appear on the display.
76 • vacon CONTROL KEYPAD Fault type symbol A (Alarm) F (Fault) AR (Fault Autoreset) FT (Fault Trip) Table 9-3. Fault types 9.3.4.2 Meaning This type of fault is a sign of an unusual operating condition. It does not cause the drive to stop, nor does it require any special actions. The 'A fault' remains in the display for about 30 seconds. An 'F fault' is a kind of fault that makes the drive stop. Actions need to be taken in order to restart the drive.
CONTROL KEYPAD 9.3.5 vacon • 77 Fault history menu (M5) The Fault history menu can be entered from the Main menu by pushing the Menu button right when the location indication M5 is visible on the first line of the keypad display. Find the fault codes in Table 11-2. All faults are stored in the Fault history menu in which you can browse through them using the Browser buttons. Additionally, the Fault time data record pages (see Chapter 9.3.4.2) are accessible at each fault.
78 • vacon 9.3.6 CONTROL KEYPAD System menu (M6) The System menu can be entered from the main menu by pushing the Menu button right when the location indication M6 is visible on the display. The controls associated with the general use of the frequency converter, such as application selection, customised parameter sets or information about the hardware and software are located under the System menu. The number of submenus and subpages is shown with the symbol S (or P) on the value line.
CONTROL KEYPAD P6.7.3 P6.7.4 S6.8 S6.8.1 C6.8.1.1 C6.8.1.2 C6.8.1.3 S6.8.2 T6.8.2.1 HMI acknowledg. timeout HMI number of retries System information Total counters MWh counter Power On day counter Power On hours counter I6.8.5.2 I6.8.5.3 I6.8.5.4 S6.8.
80 • vacon 9.3.6.1 CONTROL KEYPAD Language selection The Vacon control keypad offers you the possibility to control the frequency converter through the keypad in the language of your choice. Locate the language selection page under the System menu. Its location indication is S6.1. Press the Menu button right once to enter the edit mode. As the name of the language starts to blink you are able to choose another language for the keypad texts.
CONTROL KEYPAD vacon • 81 STOP STOP READY READY I/O term I/Oterm Application System Menu Standard S1 S11 STOP STOP READY Application Standard READY I/O term I/Oterm enter Application Multi-step Figure 9-10. Change of application 9.3.6.3 Copy parameters The parameter copy function is used when the operator wants to copy one or all parameter groups from one drive to another or to store parameter sets in the internal memory of the converter.
82 • vacon CONTROL KEYPAD READY READY Parameter sets Parameter sets Select LoadFactDef READY enter CONFIRM CANCEL READY Parameter sets Parameter sets Wait... OK Figure 9-11. Storing and loading of parameter sets Upload parameters to keypad (To keypad, S6.3.2) This function uploads all existing parameter groups to the keypad provided that the drive is stopped. Enter the To keypad page (S6.3.2) from the Parameter copy menu. Push the Menu button right to enter the edit mode.
CONTROL KEYPAD vacon • 83 Automatic parameter backup (P6.3.4) On this page you can activate or inactivate the parameter backup function. Enter the edit mode by pressing the Menu button right. Choose Yes or No with the Browser buttons. When the Parameter backup function is activated Vacon NX control keypad makes a copy of the parameters of the presently used application. Every time a parameter is changed the keypad backup is automatically updated.
84 • vacon CONTROL KEYPAD READY READY Set1 ParamComparison 0 C1 C3 OR READY READY Set1 P2.1.2= 50.0 P1 P6 20.0 Hz READY EDIT VALUE P2.1.2= 50.0 20.0 Hz enter CONFIRM CHANGE Figure 9-13. Parameter comparison 9.3.6.5 Security NOTE: The Security submenu is protected with a password. Store the password in a safe place! Password (S6.5.1) The application selection can be protected against unauthorised changes with the Password function (S6.5.1).
CONTROL KEYPAD vacon • 85 Parameter lock (P6.5.2) This function allows the user to prohibit changes to the parameters. If the parameter lock is activated the text *locked* will appear on the display if you try to edit a parameter value. NOTE: This function does not prevent unauthorised editing of parameter values. Enter the edit mode by pushing the Menu button right. Use the Browser buttons to change the parameter lock status.
86 • vacon CONTROL KEYPAD Multimonitoring items (P6.5.4) Vacon alpha-numeric keypad features a display where you can monitor even three actual values at the same time (see chapter 9.3.1 and chapter Monitoring values in the manual of the application you are using). On page P6.5.4 of the System Menu you can define if it is possible for the operator to replace the values monitored with other values. See below. READY READY I/O term READY I/Oterm I/Oterm Multimon. items Multimon.
CONTROL KEYPAD vacon • 87 Default page in the operating menu (P6.6.2) Here you can set the location (page) in the Operating menu (in special applications only) to which the display automatically moves as the set Timeout time (see below) has expired or as the power is switched on to the keypad. See setting of Default page above. Timeout time (P6.6.3) The Timeout time setting defines the time after which the keypad display returns to the Default page (P6.6.1) see above.
88 • vacon CONTROL KEYPAD Note! The brake resistor is available as optional equipment for all classes. It can be installed internally in classes FR4 to FR6. READY READY READY I/Oterm I/Oterm I/Ot erm HW settings System Menu InternBrakeRes P1 P4 S1 S8 READY Connected READY I/Oterm I/Oterm InternBrakeRes enter Connected InternBrakeRes Not conn. Figure 9-21. Internal brake resistor connection Fan control (P6.7.2) This function allows you to control the frequency converter’s cooling fan.
CONTROL KEYPAD vacon • 89 Example: Transfer delay between the frequency converter and the PC = 600 ms The value of par. 6.7.3 is set to 1200 ms (2 x 600, sending delay + receiving delay) The corresponding setting shall be entered in the Misc -part of the file NCDrive.ini: Retries = 5 AckTimeOut = 1200 TimeOut = 6000 It must also be considered that intervals shorter than the AckTimeOut-time cannot be used in NCDrive monitoring. Enter the edit mode by pushing the Menu button right.
90 • vacon CONTROL KEYPAD Trip counters (S6.8.2) Trip counters (menu S6.8.2) are counters the values of which can be reset i.e. restored to zero. You have the following resettable counters at your disposal. See Table 9-6 for examples. Note! The trip counters run only when the motor is running. Page Counter T6.8.2.1 MWh counter T6.8.2.3 Operation day counter T6.8.2.4 Operation hour counter Table 9-7. Resettable counters The counters can be reset on pages 6.8.2.2 (Clear MWh counter) and 6.8.2.
CONTROL KEYPAD vacon • 91 Applications (S6.8.4) At location S6.8.4 you can find the Applications submenu containing information about not only the application currently in use but also all other applications loaded into the frequency converter. The information available is: Page Content 6.8.4.# Name of application 6.8.4.#.1 Application ID 6.8.4.#.2 Version 6.8.4.#.3 Firmware interface Table 9-9. Applications information pages I/Oterm I/Oterm Standard D1 D3 READY A1 I/Oterm A7 2.
92 • vacon CONTROL KEYPAD For more information on the expander board-related parameters, see Chapter 9.3.7. I/Oterm I/Oterm B:NXOPTA2 E1 E2 READY I/Oterm Expander boards E1 E5 Software version 10001.0 READY READY I/Oterm A:NXOPTA1 E1 E2 I/Oterm State Run Figure 9-26. Expander board information menus Debug menu (S6.8.7) This menu is meant for advanced users and application designers. Contact factory for any assistance needed. 9 Tel.
CONTROL KEYPAD 9.3.7 vacon • 93 Expander board menu (M7) The Expander board menu makes it possible for the user 1) to see what expander boards are connected to the control board and 2) to reach and edit the parameters associated with the expander board. Enter the following menu level (G#) with the Menu button right. At this level, you can browse through slots (see page 56) A to E with the Browser buttons to see what expander boards are connected.
94 • vacon 10. COMMISSIONING COMMISSIONING 10.1 Safety Before commissioning, note the following directions and warnings: 1 2 3 4 5 6 Internal components and circuit boards of the frequency converter (except for the galvanically isolated I/O terminals) are live when Vacon NX is connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
COMMISSIONING 7 vacon • 95 Set the parameters of group 1 (See Vacon All in One Application Manual) according to the requirements of your application. At least the following parameters should be set: - motor nominal voltage motor nominal frequency motor nominal speed motor nominal current You will find the values needed for the parameters on the motor rating plate.
96 • vacon 10 Connect the motor to the process (if the startup test was run without the motor being connected) a) Before running the tests, make sure that this can be done safely. b) Inform your co-workers of the tests. c) Repeat test 8A or 8B. 10 Tel.
FAULT TRACING 11. vacon • 97 FAULT TRACING The fault codes, their causes and correcting actions are presented in Table 11-2 below. The converter has an internal memory for storing the converter status at the time of fault as well as additional information about the source of the fault. This feature is intended to help the user or the service personnel to determine the cause of fault. 11.1 Fault time data record When a fault occurs a fault code is displayed on the keypad.
98 • vacon FAULT TRACING Real time record If real time is set to run on the frequency converter the data items T1 and T2 will appear as follows: T.1 T.2 Date Time yyyy-mm-dd hh:mm:ss,sss Note: When contacting your Vacon partner because of a fault condition, always write down all texts and codes on the keypad display before. 11.2 Fault codes The fault codes, their causes and correcting actions are presented in the table below. The shadowed faults are A faults only.
FAULT TRACING 8 System fault 9 Undervoltage 10 11 12 13 Input line supervision Output phase supervision Brake chopper supervision vacon • 99 - component failure - faulty operation Note exceptional fault data record Subcode in T.
100 • vacon 18 Unbalance (Warning only) 22 EEPROM checksum fault 24 Counter fault 25 26 29 31 32 34 35 37 38 39 40 11 FAULT TRACING Should the fault re-occur, contact your local distributor. Microprocessor watchdog fault Unbalance between power modules in paralleled units. Subcode in T.
FAULT TRACING vacon • 101 43 Encoder fault 44 Device changed (different type) 45 Device added (different type) Option board of different type added. 49 Div by zero in application A division by zero has occurred in the application program. 50 Current at the analogue input is < 4mA. control cable is broken or loose signal source has failed 53 Analogue input Iin < 4mA (sel.
Vacon distributor: