User Manual

MCN Remote Comparator Display Troubleshooting
CTI Products, Inc.
68-10856-210
64
Problem:
I cannot get the HIB and PC to communicate through my leased line
connection.
Verify that the baud rate specified on the MCNRCD command line matches
the settings of the HIB’s OPTION A switches 1, 2 and 3. Either change the
command line baud rate setting or change the HIB’s baud rate switches and
reset the HIB.
Verify that the HIB’s OPTION A switch 5 is in the UP position. If not in the
UP position, change the switch and reset the HIB.
Verify that you specified the
/LL
command line option for MCNRCD.