Owner's manual
MCN Config Program: Display Tables Window
67 68-11824-210
State Priority
The states in the table have the following priority:
1. Off-Line If the module is off-line.
2. Numbered States Lowest number has the highest priority.
3. Default State If no other state is found to match the input bits.
If an input value is covered by two defined states, the lower numbered state will be displayed.
State Text & Color Field
This is free-format text to be displayed when this state is active.
Foreground and background colors can be defined for each state.
Sound Field
This field is the .WAV sound file to be played whenever any input changes to this state. This
field is typically used only for alarm conditions.
Sounds are played only if the state is also logged. If you want a sound to play for a state entry,
make sure the Log field is set to 1.
Email Field
This is a flag to determine whether or not to log this state to email.
0 = Don't log
1 = Log
If the Logging flag is set to 1, an email log entry will be generated whenever an input goes into
or out of this state.
Log Field
This is a flag to determine whether or not to log this state (to screen, printer, or disk).
0 = Don't log
1 = Log
If the Log flag is set to 1, a log entry will be generated whenever an input goes into or out of
this state.