7.1.1 Address Planning
To help organize the MCN system, we have provided the following guidelines for
assigning unit addresses:
Assign all Comparator I/O Modules to the same Group or set of
Groups (if you have more than 16 modules), typically beginning with
Group 00, Module 0 and progressing sequentially. Although modules
can be added at higher addresses later, if you have plans to expand a
channel, you may want to leave a module addresses open for the
expansion.
Assign all User Interface Modules to the same Group or set of Groups
(if you have more than 16 modules), beginning with Group 80, Module
0.
If you have multiple MCN systems in remote locations and you plan to
tie them together with a EXB Module, use unique addresses
throughout all your systems. Start the Comparator I/O modules and
User Interface Modules at each location with new group numbers.
This will allow you to connect the systems without re-addressing the
modules.
When using the HIB User Interface Module with the MCN Remote
Comparator Display software, only four Groups can be monitored and
controlled at a time on one PC. If you are going to be using this User
Interface Module, plan the addresses of your Comparator I/O modules
so that you use as few different Groups as possible.
In a large system, you can monitor and control more than 4 Groups on
a PC using the HIB; you are just limited to 4 groups simultaneously.
For these types of large systems, group your modules so that all the
receivers you may want to watch simultaneously are within the same 4
groups.