Technical data
65
CTC EcoZenith i250 
Installation
13.5.1  Remote-controlled temperature reduction
The night temperature reduction function can be activated via a closed 
function on the electricity remote control input, pins G33 and G34 on the 
terminal board. The function can be controlled remotely using “Minicall”, for 
instance. 
While the input is short circuited, the temperature reduction is activated, 
regardless of other settings. When the short circuit ceases, the product 
returns to ordinary settings. 
The size of the reduction is set in the menu: Installer/Settings/Radiator 
system/Prim reduced.
NOTE: the input function can be selected according to the following:
•  NR = Night reduction of temperature (time-controlled lowering of 
temperature)
•  SO = Shut off (compressor and power output blocked by the electricity 
supplier)
•  DHW = Extra hot water button (accessory) 
13.5.2 Current sensor connection
The three current sensors (designated current transformer on the connection 
block), one for each phase, are fitted on the fuse panel in the following 
manner.
Each phase from the electricity distribution board supplying the EcoHeat 
is channelled through a current sensor before termination at the relevant 
terminal. Then connect to the boiler based on the terminal board diagram. 
This allows the phase current to be sensed all the time and compared with 
the value set for the EcoZenith’s current monitor. If the current is higher, the 
control unit drops to a lower heat output. If it is still too high, further reduction 
in output takes place.
When the current has dropped below the set value again, the output will 
increase. 
This means that the current sensors, along with the electronics, prevent 
more power being supplied than the main fuses can tolerate.
L1
L2
L3
1
2
3
4
1
2
3
4
From electricity meter
Current 
sensor
Fuse panel
To boiler
Low current
Connection block
Use at least 0.5 mm
2 
cable.
L1
L2
L3
1
2
3
4
1
2
3
4










