Technical data
35  CTC EcoZenith i250
General Information
8.7.3  Immersion heater
Upper boiler °C  50 (30 to 60)
Temperature when the immersion heater kicks in 
and helps EcoZenith i250 to produce domestic hot 
water when there is great demand. A low setting is 
recommended. 
The immersion heater is also responsible for providing 
the house with additional heating. If the house requires 
a higher temperature than that selected, the control 
system compensates by automatically raising the 
temperature of the immersion heaters.
This temperature also reflects the settings chosen under 
DHW. 
Upper boiler add heat °C  57 (30 to 70)
The temperature of the boiler when EcoZenith i250 
calls for assistance to reach the high temperature; the 
immersion heater then works up to this value after the 
set time delay on the mixing valve.
Upper boiler extra DHW  60 (30 to 70)
This means the boiler is to provide extra DHW. This 
setting determines whether the electric heater should 
help to produce extra hot water. Set the temperature 
of the electric unit to the desired value when the option 
for extra hot water is activated under the DHW menu. 
A lower value means that the heat pump produces the 
majority of hot water, not the immersion heater.
Upper boiler max. kW  5.5 (0 to 9.0)
You set the max. permitted power for the immersion 
heater here. 
Setting for the maximum permitted power for the 
electric unit. 0 to 9.0 kW in steps of 0.3 kW.
Lower boiler °C  55 (30 to 70)
Setting for the temperature of the lower immersion 
heater.
1 2
1 2
T ºC
60
40
20
0
-20
16  20  0  4  8 12
Room temp.
Heating circuit 1
Night reduction Holiday
Room temp.
Heating circuit 1 (50)
Night reduction Holiday
Heat pump
Compressor Permitted
Min outdoor temp °C  -15
Brine pump on 10 days  0
Tariff HP  Off
Minimum run time  6
Electric heater
Boiler upper°C  50
Boiler upper add°C  57
Boiler upper extra DHW°C  60
Boiler upper max kW  5.5
Boiler lower °C  55
Boiler lower max kW  6.0
Delay mixing valve  180
Main fuse A  25
Input voltage  3x400 V
Upper tank
Stop temp HP°C  Max
Start/stop diff upper ºC  7
Max time upper tank  20
Max time lower tank  40
Communication
MB address  1
Baud rate  9600
Parity  even
Stop bit  1
Save settings
Save settings?
Def Heat pump
Heat pump  Off
Flow/level switch  None
Test Heating circuit
Mixing valve1  Open
Rad pump1  On
Mixing valve2  Off
Rad pump2  Off
LED room sensor  On
Test valves
Test Elec.heater
3-way valve  Down
Electric heater L1A  Off
Electric heater L1B  Off
Electric heater L2A  Off 
Electric heater L2B  Off
Electric heater L3A  Off
Electric heater L3B  Off
Electric heater A13  Off
Alarm log 
Latest alarm:  Time  HP (b)  LP (b)  SH (K)  I(A)
Low brine flow  07:20 6/3  8.8  3.3  15.9  3.9
Stored alarms:
Wrong phase order  10:30 1/3  27.9  8.6  -227  50.0
Comm. error motor protect  09:01 1/3 27.9  3.6  42.2 
0.0
Factory settings coded
Code  0 0 0 0
Upper tank 
Lower tank
Compressor operation
Expansion valve
Log compressor stop
Operation data heating 2
Out  Room1 Prim1  Return Room2  Prim2
Test Heat pump
HP Compr.  Off
HP Brine p/Fan  Off
HP Charge p  0
Defrost Manually  Off
Compressor heat  Off
Drip tray heater  Off
Heating Cable  Off
4-way valve(Y11)  Off
Tariff HP
This is used when a dual tariff is used with lower energy 
costs at set hours of the day. The heat pump can then 
take advantage of reduced primary energy costs. It 
must be set to Off.
Min oper. time  6 (0 to 20)
Minimum operating time in minutes that the compressor 
is permitted to operate. Even if the tank’s stop 
temperature has been achieved, the compressor 
continues to supply energy during this period. 










