Technical data
32
CTC EcoZenith i250
General Information
Installer
8.6 Installer
This menu contains four sub-menus: Time/Language,
Settings, Define system and Service.
Time/Language includes time and language settings for
your CTC EcoZenith i250.
Settings are used both by the installer and users for
installing the system.
Define system is used by the installer to define your
heating system.
Service is used for troubleshooting and diagnosis. You
will find here the options Function test, Alarm history,
Factory settings code, Quick start compressor and
Software update.
8.6.1 Time/Language
You use this to set the date and time. The clock saves
the settings in the event of a power cut. Summer/winter
time is changed automatically.
Time settings
When a green box appears around the time, press OK
and the first value is selected. Use the arrows to set the
correct value.
When you press OK, the next value is highlighted.
Setting the language
The current language has a green circle around it.
Svenska Nederlands English Deutsch
Suomi Française Dansk Norsk
1 2
1 2
22,2 ºC 21,2 ºC 58 ºC -5 ºC
1 2
1 2
1 2
06 - 09 18 - 21
07 - 09 20 - 23
06 - 09 10 - 21
06 - -- -- - 21
06 - -- -- - 21
10 - 12 20 - 23
10 - 12 20 - 23
1 2
1 2
T ºC
60
40
20
0
-20
16 20 0 4 8 12
06-09 18-21
07-09 00-00
06-09 00-00
06-09 00-00
06-09 00-00
10-12 00-00
10-12 00-00
Room temp. DHW Operation Installer
CTC EcoZenith Monday 09:35
Night reduction Holiday
Heating circuit 2 (50)
Heating circuit 1
Room temp.
Start menu
Room temperature settings
Selecting DHW comfort
Heating system data
Installer settings menu
Extra
Hot water
0.0 hours
On
Temperature
Normal
Weekly schedule
DHW
Weekly program Day by day
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Weekly program DHW
Operation data system
Status HP upper tank
Tank upper°C 49 (60)
Tank lower°C 42 (45)
Primary flow°C 42 (43)
Return flow°C 34
Radiator pump On
Mixing valve Open
Delay mixing valve 180
Electric power kW 0.0 0.0 0.0
Current L1/L2/L3 0.0 0.0 0.0
Operation data EcoZenith
Stored oper data
Heating circuit 2
Operation data heating
Installer
Time/Language Settings Define system Service
Software display PCB: 20120205
Software HP PCB: 20120125
Installer
Installer
Time 21:34
Date 2012-02-05
Settings
Heating circuit
Heating circuit 1
Heating circuit 2
Heat pump
Electric heater
Upper tank
Remote control NR
Communication
Save settings
Load settings
Load factory settings
Max primary flow°C 55
Min primary flow°C Off
Heating off, out°C 18
Heating off 120
Inclination°C 50
Adjustment°C 0
Room temp reduced°C -2
or
Primary flow reduced°C -3
Define system
Def heating circuit
Heating circuit 1
Heating circuit 2
Heat pump
SMS
Cooling
Heating circuit 1 Yes
Room sensor 1 Yes
Type Wire
Service
Function test
Function test
Alarm log
Factory settings coded
Quick start compressor.
Software update, USB
Write log to USB
Control current sensors
Re-installation
Heating circuit
Heat pump
Valves
Electric heater
Total operation time h: 14196
Max primary flow°C: 51
Consumtion kWh 20
Compressor:
Operation time /24 h:m 00:00
Stored oper data
Heat pump
Compressor On
Charge pump On 47%
Brine pump On
HP in/out°C 35.5 / 42.3
Current L1 4.0
Night reduction heat circ.
Weekly program Day by day NR
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Night reduction heat circ.
Weekly program Block NR
Decrease Sunday 22:00
Increase Friday 14:00
Decrease -------- 00:00
Increase -------- 00:00
Holiday
Holiday period 3 days
Out Room1 Prim1 Return Room2 Prim2
Svenska Nederlands English Deutsch
Suomi Française Dansk Norsk
1 2
1 2
22,2 ºC 21,2 ºC 58 ºC -5 ºC
1 2
1 2
1 2
06 - 09 18 - 21
07 - 09 20 - 23
06 - 09 10 - 21
06 - -- -- - 21
06 - -- -- - 21
10 - 12 20 - 23
10 - 12 20 - 23
1 2
1 2
T ºC
60
40
20
0
-20
16 20 0 4 8 12
06-09 18-21
07-09 00-00
06-09 00-00
06-09 00-00
06-09 00-00
10-12 00-00
10-12 00-00
Room temp. DHW Operation Installer
CTC EcoZenith Monday 09:35
Night reduction Holiday
Heating circuit 2 (50)
Heating circuit 1
Room temp.
Start menu
Room temperature settings
Selecting DHW comfort
Heating system data
Installer settings menu
Extra
Hot water
0.0 hours
On
Temperature
Normal
Weekly schedule
DHW
Weekly program Day by day
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Weekly program DHW
Operation data system
Status HP upper tank
Tank upper°C 49 (60)
Tank lower°C 42 (45)
Primary flow°C 42 (43)
Return flow°C 34
Radiator pump On
Mixing valve Open
Delay mixing valve 180
Electric power kW 0.0 0.0 0.0
Current L1/L2/L3 0.0 0.0 0.0
Operation data EcoZenith
Stored oper data
Heating circuit 2
Operation data heating
Installer
Time/Language Settings Define system Service
Software display PCB: 20120205
Software HP PCB: 20120125
Installer
Installer
Time 21:34
Date 2012-02-05
Settings
Heating circuit
Heating circuit 1
Heating circuit 2
Heat pump
Electric heater
Upper tank
Remote control NR
Communication
Save settings
Load settings
Load factory settings
Max primary flow°C 55
Min primary flow°C Off
Heating off, out°C 18
Heating off 120
Inclination°C 50
Adjustment°C 0
Room temp reduced°C -2
or
Primary flow reduced°C -3
Define system
Def heating circuit
Heating circuit 1
Heating circuit 2
Heat pump
SMS
Cooling
Heating circuit 1 Yes
Room sensor 1 Yes
Type Wire
Service
Function test
Function test
Alarm log
Factory settings coded
Quick start compressor.
Software update, USB
Write log to USB
Control current sensors
Re-installation
Heating circuit
Heat pump
Valves
Electric heater
Total operation time h: 14196
Max primary flow°C: 51
Consumtion kWh 20
Compressor:
Operation time /24 h:m 00:00
Stored oper data
Heat pump
Compressor On
Charge pump On 47%
Brine pump On
HP in/out°C 35.5 / 42.3
Current L1 4.0
Night reduction heat circ.
Weekly program Day by day NR
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Night reduction heat circ.
Weekly program Block NR
Decrease Sunday 22:00
Increase Friday 14:00
Decrease -------- 00:00
Increase -------- 00:00
Holiday
Holiday period 3 days
Out Room1 Prim1 Return Room2 Prim2
Svenska Nederlands English Deutsch
Suomi Française Dansk Norsk
1 2
1 2
22,2 ºC 21,2 ºC 58 ºC -5 ºC
1 2
1 2
1 2
06 - 09 18 - 21
07 - 09 20 - 23
06 - 09 10 - 21
06 - -- -- - 21
06 - -- -- - 21
10 - 12 20 - 23
10 - 12 20 - 23
1 2
1 2
T ºC
60
40
20
0
-20
16 20 0 4 8 12
06-09 18-21
07-09 00-00
06-09 00-00
06-09 00-00
06-09 00-00
10-12 00-00
10-12 00-00
Room temp. DHW Operation Installer
CTC EcoZenith Monday 09:35
Night reduction Holiday
Heating circuit 2 (50)
Heating circuit 1
Room temp.
Start menu
Room temperature settings
Selecting DHW comfort
Heating system data
Installer settings menu
Extra
Hot water
0.0 hours
On
Temperature
Normal
Weekly schedule
DHW
Weekly program Day by day
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Weekly program DHW
Operation data system
Status HP upper tank
Tank upper°C 49 (60)
Tank lower°C 42 (45)
Primary flow°C 42 (43)
Return flow°C 34
Radiator pump On
Mixing valve Open
Delay mixing valve 180
Electric power kW 0.0 0.0 0.0
Current L1/L2/L3 0.0 0.0 0.0
Operation data EcoZenith
Stored oper data
Heating circuit 2
Operation data heating
Installer
Time/Language Settings Define system Service
Software display PCB: 20120205
Software HP PCB: 20120125
Installer
Installer
Time 21:34
Date 2012-02-05
Settings
Heating circuit
Heating circuit 1
Heating circuit 2
Heat pump
Electric heater
Upper tank
Remote control NR
Communication
Save settings
Load settings
Load factory settings
Max primary flow°C 55
Min primary flow°C Off
Heating off, out°C 18
Heating off 120
Inclination°C 50
Adjustment°C 0
Room temp reduced°C -2
or
Primary flow reduced°C -3
Define system
Def heating circuit
Heating circuit 1
Heating circuit 2
Heat pump
SMS
Cooling
Heating circuit 1 Yes
Room sensor 1 Yes
Type Wire
Service
Function test
Function test
Alarm log
Factory settings coded
Quick start compressor.
Software update, USB
Write log to USB
Control current sensors
Re-installation
Heating circuit
Heat pump
Valves
Electric heater
Total operation time h: 14196
Max primary flow°C: 51
Consumtion kWh 20
Compressor:
Operation time /24 h:m 00:00
Stored oper data
Heat pump
Compressor On
Charge pump On 47%
Brine pump On
HP in/out°C 35.5 / 42.3
Current L1 4.0
Night reduction heat circ.
Weekly program Day by day NR
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Night reduction heat circ.
Weekly program Block NR
Decrease Sunday 22:00
Increase Friday 14:00
Decrease -------- 00:00
Increase -------- 00:00
Holiday
Holiday period 3 days
Out Room1 Prim1 Return Room2 Prim2