Technical data

39 CTC EcoZenith i250
General Information
Delay mixing valve 180 (30...240, blocked)
The mixing valve delay, the period before it draws
energy from the immersion heater, is set here. It can
be set from 30 to 240 minutes. If the value is set to
”Blocked”, the mixing valve will never open to the boiler.
(Blocked)
Main fuse A 20 (10...35)
The property’s main fuse size is set here. This setting
and the fitted current sensors ensure the fuses are
protected when using appliances which generate
temporary power peaks, for example, cookers, ovens,
engine heaters, etc. The product temporarily reduces
power drawn where this type of equipment is being
used.
Input voltage 3x400 V
The value is set here to indicate whether the CTC
EcoZenith is connected at 3x400 V, 1x230 V or 3x230
V. 3x400 V and 1x230 V are valid for the UK.
Tariff, EL Off
Not applicable. Applies only to products marked “Tariff”.
It must be set to Off.
8.7.4 Upper tank
(Applies only if a heat pump has been installed.)
Stop temp HP °C Max. (40...58, Max.)
At this temperature, the heat pump stops charging the
upper tank.
Start/stop diff upper °C 7 (3...10)
Hysteresis before the heat pump starts or stops
charging the upper tank.
Max. time upper tank 20 (10...150)
This is the maximum time in minutes spent by the heat
pump charging the upper tank if required in the lower
tank.
Max. time lower tank 40 (10...120)
This is the maximum time in minutes spent by the heat
pump charging the lower tank if required in the upper
tank.
1 2
1 2
T ºC
60
40
20
0
-20
16 20 0 4 8 12
Radiatorsystem forts
58 ºC -5 ºC
Info golvtorkning estricht
Room temp.
Heating circuit 1
Night reduction Holiday
Room temp.
Heating circuit 1 (50)
Night reduction Holiday
Set. heat pump
Compressor Permitted
1
Min outdoor temp °C -15
2
Brine pump on Auto
Tariff HP Off
Minimum run time 6
Electric heater
Boiler upper°C 50
Boiler upper add°C 57
Boiler upper extra DHW°C 60
Boiler upper max kW 5.5
Boiler lower °C 55
Boiler lower max kW 6.0
Delay mixing valve 180
Main fuse A 25
Input voltage 3x400 V
Tariff EL Off
Upper tank
Stop temp HP°C Max
Start/stop diff upper ºC 7
Max time upper tank 20
Max time lower tank 40
Communication
MB address 1
Baud rate 9600
Parity even
Stop bit 1
Installer
Save settings
Save settings
Load factory settings
Def Heat pump
Heat pump Off
Flow/level switch None
Test Heating circuit
Mixing valve1 Open
Rad pump1 On
Mixing valve2 Off
Rad pump2 Off
LED room sensor On
Test valves
Test Elec.heater
3-way valve Down
Electric heater L1A Off
Electric heater L1B Off
Electric heater L2A Off
Electric heater L2B Off
Electric heater L3A Off
Electric heater L3B Off
Electric heater A13 Off
Alarm log
Latest alarm: Time HP (b) LP (b) SH (K) I(A)
Low brine flow 07:20 6/3 8.8 3.3 15.9 3.9
Stored alarms:
Wrong phase order 10:30 1/3 27.9 8.6 -227 50.0
Com. err m. protect 09:01 1/3 27.9 3.6 42.2 0.0
Factory settings coded
Code 0 0 0 0
Upper tank
Lower tank
Compressor operation
Expansion valve
Log compressor stop
Cooling
Operation data heating 2
Out Room1 Prim1 Return Room2 Prim2
Test Heat pump
HP Compr. Off
HP Brine p/Fan Off
HP Charge p 0
Defrost Manually Off
Compressor heat Off
Drip tray heater Off
Heating Cable Off
4-way valve(Y11) Off
Inst. Radiatorsystem1
<<
Anti Water Hammer No
HP max DHW Yes
Drying period mode Off
Drying period temp ºC 25
Room temp. DHW Operation Installer
Drying period activ 1 / 12 (25)
CTC EcoZenith Monday 09:35