Technical data
36
CTC EcoZenith i250 
General Information
Drying period mode  Off (Off/1/2/3)
Floor drying function for newly-built properties. 
The function limits the calculation of primary flow 
temperature (setpoint) for “Your home’s heating 
installation” to the schedule below.
Mode 1
Floor drying function for 8 days.
1. The (setpoint) of the radiator system is set to 25ºC for 
4 days. 
2. On Days 5–8, the value set in “Floor function temp. 
ºC” is used.
(From Day 9 onwards the value is calculated 
automatically according to “Your home’s heating 
installation”)
Mode 2
Floor drying function for 10 days + stepped increase 
and decrease.
1. Stepped increase start: The (setpoint) of the 
radiator system is set to 25ºC. The (setpoint) is 
then raised by 5ºC each day until its (setpoint) is 
equal to the “Floor function temp. ºC”.
The final step may be less than 5ºC.
3. Stepped decrease: After the stepped increase 
and 10 days at an even temperature, the 
temperature (setpoint) is reduced to 25ºC in daily 
5ºC stages.
The final step may be less than 5ºC.
(Following the stepped decrease and one 
day at the (setpoint) of 25ºC the value is calculated 
automatically according to “Your home’s heating 
installation”.)
Mode 3
In this mode, the function starts in Mode 1 and this is 
then followed by Mode 2 and finally by “Your home’s 
heating installation”.
Floor function temp. ºC  25 (25...55)
Here you set the temperature for Mode 1/2/3 as shown 
above.
1 2
1 2
T ºC
60
40
20
0
-20
16  20  0  4  8 12
Radiatorsystem forts
  58 ºC  -5 ºC
Info golvtorkning estricht
Room temp.
Heating circuit 1
Night reduction Holiday
Room temp.
Heating circuit 1 (50)
Night reduction Holiday
Set. heat pump
Compressor   Permitted
1
Min outdoor temp °C  -15
2
Brine pump on    Auto
Tariff HP    Off
Minimum run time    6
Electric heater
Boiler upper°C    50
Boiler upper add°C    57
Boiler upper extra DHW°C  60
Boiler upper max kW    5.5
Boiler lower °C    55
Boiler lower max kW    6.0
Delay mixing valve    180
Main fuse A    25
Input voltage    3x400 V
Tariff EL    Off
Upper tank
Stop temp HP°C    Max
Start/stop diff upper ºC  7
Max time upper tank    20
Max time lower tank    40
Communication
MB address    1
Baud rate    9600
Parity   even
Stop bit    1
Installer
Save settings
Save settings
Load factory settings
Def Heat pump
Heat pump  Off
Flow/level switch  None
Test Heating circuit
Mixing valve1    Open
Rad pump1    On
Mixing valve2    Off
Rad pump2    Off
LED room sensor    On
Test valves
Test Elec.heater
3-way valve    Down
Electric heater L1A    Off
Electric heater L1B    Off
Electric heater L2A    Off
Electric heater L2B    Off
Electric heater L3A    Off
Electric heater L3B    Off
Electric heater A13    Off
Alarm log 
Latest alarm:  Time  HP (b) LP (b)  SH (K)  I(A)
Low brine flow  07:20 6/3  8.8  3.3  15.9  3.9
Stored alarms:
Wrong phase order  10:30 1/3  27.9  8.6  -227  50.0
Com. err m. protect 09:01 1/3  27.9  3.6  42.2  0.0
Factory settings coded
Code  0 0 0 0
Upper tank 
Lower tank
Compressor operation
Expansion valve
Log compressor stop
Cooling
Operation data heating 2
Out  Room1 Prim1  Return Room2  Prim2
Test Heat pump
HP Compr.    Off
HP Brine p/Fan    Off
HP Charge p    0
Defrost Manually    Off
Compressor heat    Off
Drip tray heater    Off
Heating Cable    Off
4-way valve(Y11)    Off
Inst. Radiatorsystem1
<<
Anti Water Hammer    No
HP max DHW    Yes
Drying period mode    Off
Drying period temp ºC  25
 Room temp.  DHW  Operation  Installer
  Drying period activ  1  /  12  (25)
CTC EcoZenith  Monday 09:35
Example for operation data Mode 2, Day 1 of 12 with 
current (setpoint) 25ºC.
Day
1 2 3 4 5 6 7 8  9 etc... 
65 
60 
55 
50 
45 
40 
35 
30 
25 
20
ºC
Example for Mode 1 with “Floor function temp. 38ºC”.
“Your home’s heating 
installation”
1.
2.
“Your home’s heating 
installation”
1. 3.2. 10 days
Example for Mode 2 with “Floor function temp. 37ºC”.
1  2  3   4  5  6  7 8  9  10   11 12  13 etc...
65 
60 
55 
50 
45 
40 
35 
30 
25 
20
ºC
Day










