Technical data

24
CTC EcoZenith i250
General Information
Night reduction Holiday
The example above shows that the room temperature is 22.4
°C and the desired value (setpoint) is 23.5 °C.
1 2
1 2
T ºC
60
40
20
0
-20
16 20 0 4 8 12
Radiatorsystem forts
58 ºC -5 ºC
Info golvtorkning estricht
Room temp.
Heating circuit 1
Night reduction Holiday
Room temp.
Heating circuit 1 (50)
Night reduction Holiday
Set. heat pump
Compressor Permitted
1
Min outdoor temp °C -15
2
Brine pump on Auto
Tariff HP Off
Minimum run time 6
Electric heater
Boiler upper°C 50
Boiler upper add°C 57
Boiler upper extra DHW°C 60
Boiler upper max kW 5.5
Boiler lower °C 55
Boiler lower max kW 6.0
Delay mixing valve 180
Main fuse A 25
Input voltage 3x400 V
Tariff EL Off
Upper tank
Stop temp HP°C Max
Start/stop diff upper ºC 7
Max time upper tank 20
Max time lower tank 40
Communication
MB address 1
Baud rate 9600
Parity even
Stop bit 1
Installer
Save settings
Save settings
Load factory settings
Def Heat pump
Heat pump Off
Flow/level switch None
Test Heating circuit
Mixing valve1 Open
Rad pump1 On
Mixing valve2 Off
Rad pump2 Off
LED room sensor On
Test valves
Test Elec.heater
3-way valve Down
Electric heater L1A Off
Electric heater L1B Off
Electric heater L2A Off
Electric heater L2B Off
Electric heater L3A Off
Electric heater L3B Off
Electric heater A13 Off
Alarm log
Latest alarm: Time HP (b) LP (b) SH (K) I(A)
Low brine flow 07:20 6/3 8.8 3.3 15.9 3.9
Stored alarms:
Wrong phase order 10:30 1/3 27.9 8.6 -227 50.0
Com. err m. protect 09:01 1/3 27.9 3.6 42.2 0.0
Factory settings coded
Code 0 0 0 0
Upper tank
Lower tank
Compressor operation
Expansion valve
Log compressor stop
Cooling
Operation data heating 2
Out Room1 Prim1 Return Room2 Prim2
Test Heat pump
HP Compr. Off
HP Brine p/Fan Off
HP Charge p 0
Defrost Manually Off
Compressor heat Off
Drip tray heater Off
Heating Cable Off
4-way valve(Y11) Off
Inst. Radiatorsystem1
<<
Anti Water Hammer No
HP max DHW Yes
Drying period mode Off
Drying period temp ºC 25
Room temp. DHW Operation Installer
Drying period activ 1 / 12 (25)
CTC EcoZenith Monday 09:35
8.3 Room temp.
This is used to set the desired room temperature. Use
the plus and minus buttons to set the temperature
you want, which gives you the “setpoint” temperature,
shown in brackets. You can see the current value next
to the brackets.
If two radiator systems are installed, the values for both
are displayed.
If you want to schedule a temperature reduction,
you can continue to the Night reduction or Holiday
submenus.
You can select Room sensor No under the Installer/
Define system/Radiator system menu. This can be
done if the room sensor is awkwardly positioned, if the
floor heating control has its own room sensors or if you
use a fire place or open stove. The alarm LED on the
room sensor still functions as normal.
If you use the fire or open stove only occasionally, the
firing process can affect the room sensor and reduce
the temperature supplied to the radiators. It can then
get cold in the rooms in other parts of the house. The
room sensor can temporarily be deselected during
the firing process. The EcoZenith i250 then provides
heating to the radiators using the set heating curve. The
radiator thermostats reduce the heating supplied to the
section of the house where a fire is burning.
8.3.1 Setting a room temp. without a
room sensor
If a room sensor has not been installed (this can be
selected from the Installer/Define/Radiator system
menu), the room temperature is adjusted using
this option, which displays the setting range as a
percentage. (50) denotes default setting; the heat can
be increased or decreased in variable adjustments from
this value. If this range is not sufficient, the basic setting
must be adjusted under the Installer/Settings/Radiator
system menu.
Change the value in small steps each time (approx. 2
to 3 steps) and wait for the result (approx. one day), as
there is a delay in the system responding.
Several adjustments may be necessary at different
outdoor temperatures, but you will gradually achieve the
right setting that will not need to be changed.
The example above shows how it operates with two radiator
systems. Radiator system 1 with a room sensor and radiator
system 2 without one.
Svenska Nederlands English Deutsch
Suomi Française Dansk Norsk
1 2
1 2
22,2 ºC 21,2 ºC 58 ºC -5 ºC
1 2
1 2
1 2
1 2
1 2
T ºC
60
40
20
0
-20
16 20 0 4 8 12
00 - 06 22 - 24
00 - 06 22 - 24
00 - 06 22 - 24
00 - 06 22 - 24
00 - 06 23 - 24
00 - 08 23 - 24
00 - 08 22 - 24
06 - 09 18 - 21
07 - 09 -- - --
08 - 09 -- - --
08 - -- -- - 21
08 - -- -- - 21
10 - 12 20 - 23
10 - 12 20 - 23
Room temp. DHW Operation Installer
CTC EcoZenith Monday 09:35
Night reduction Holiday
Heating circuit 2 (50)
Heating circuit 1
Room temp.
Start menu
Room temperature settings
Selecting DHW comfort
Heating system data
Installer settings menu
Extra
Hot water
0.0 hours
On
Temperature
Normal
Weekly schedule
DHW
Operation data system
Status HP upper tank
Tank upper°C 49 (58)
Tank lower°C 42 (45)
Electric power kW 0.0+2.5
Current L1/L2/L3 0.0 0.0 0.0
Diff func. Pump / ºC On 32
Pool ºC Off 22(20)
Operation data EcoZenith
Stored oper data
Heating circuit
Operation data heating
Installer
Time/Language Settings Define system Service
Software display PCB: 20120205
Software HP PCB: 01234
Installer
Installer
Time 21:34
Date 2012-02-05
Settings
Heating circuit 1
Heating circuit 1
Heating circuit 2
Heat pump
Electric heater
Upper tank
Remote control None
Communication
Solar panels
Diff thermostat function
Pool
Save settings
Load settings
Load factory settings
Max primary flow°C 55
Min primary flow°C Off
Heating off, out°C 18
Heating off 120
Inclination°C 50
Adjustment°C 0
Room temp reduced°C -2
or
Primary flow reduced°C -3
>>
Define system
Def heating circuit 1
Heating circuit 1
Heating circuit 2
Heat pump
CTC SMS
Cooling
Solar panels
Diff thermostat function No
Pool (G50, G51, B50) No
Heating circuit 1 Yes
Room sensor 1 Yes
Type Wire
Service
Function test
Function test
Alarm log
Factory settings coded
Quick start compressor.
Software update, USB
Write log to USB
Control current sensors
Re-installation
Heating circuit
Heat pump
Valves
Electric heater
Solar
Diff thermostat function
Pool
Total operation time h: 14196
Max primary flow°C: 51
Consumtion kWh 20
Compressor:
Total Operation time 1540
Stored oper data
Heat pump
Compressor On
Charge pump On 47%
Brine pump On
HP in/out°C 35.5 / 42.3
Current L1 4.0
Night reduction heat circ.
Weekly program Block NR
Decrease Sunday 22:00
Increase Friday 14:00
Decrease -------- 00:00
Increase -------- 00:00
Holiday
Holiday period 3 days
Out Room1 Prim1 Return Room2 Prim2
Settings language
Night reduction heat circ. 1
Weekly program Day by day NR
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Weekly program Day by day DHW
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Weekly program DHW
1 2
1 2
T ºC
60
40
20
0
-20
16 20 0 4 8 12
Radiatorsystem forts
58 ºC -5 ºC
Info golvtorkning estricht
Room temp.
Heating circuit 1
Night reduction Holiday
Room temp.
Heating circuit 1 (50)
Night reduction Holiday
Set. heat pump
Compressor Permitted
1
Min outdoor temp °C -15
2
Brine pump on Auto
Tariff HP Off
Minimum run time 6
Electric heater
Boiler upper°C 50
Boiler upper add°C 57
Boiler upper extra DHW°C 60
Boiler upper max kW 5.5
Boiler lower °C 55
Boiler lower max kW 6.0
Delay mixing valve 180
Main fuse A 25
Input voltage 3x400 V
Tariff EL Off
Upper tank
Stop temp HP°C Max
Start/stop diff upper ºC 7
Max time upper tank 20
Max time lower tank 40
Communication
MB address 1
Baud rate 9600
Parity even
Stop bit 1
Installer
Save settings
Save settings
Load factory settings
Def Heat pump
Heat pump Off
Flow/level switch None
Test Heating circuit
Mixing valve1 Open
Rad pump1 On
Mixing valve2 Off
Rad pump2 Off
LED room sensor On
Test valves
Test Elec.heater
3-way valve Down
Electric heater L1A Off
Electric heater L1B Off
Electric heater L2A Off
Electric heater L2B Off
Electric heater L3A Off
Electric heater L3B Off
Electric heater A13 Off
Alarm log
Latest alarm: Time HP (b) LP (b) SH (K) I(A)
Low brine flow 07:20 6/3 8.8 3.3 15.9 3.9
Stored alarms:
Wrong phase order 10:30 1/3 27.9 8.6 -227 50.0
Com. err m. protect 09:01 1/3 27.9 3.6 42.2 0.0
Factory settings coded
Code 0 0 0 0
Upper tank
Lower tank
Compressor operation
Expansion valve
Log compressor stop
Cooling
Operation data heating 2
Out Room1 Prim1 Return Room2 Prim2
Test Heat pump
HP Compr. Off
HP Brine p/Fan Off
HP Charge p 0
Defrost Manually Off
Compressor heat Off
Drip tray heater Off
Heating Cable Off
4-way valve(Y11) Off
Inst. Radiatorsystem1
<<
Anti Water Hammer No
HP max DHW Yes
Drying period mode Off
Drying period temp ºC 25
Room temp. DHW Operation Installer
Drying period activ 1 / 12 (25)
CTC EcoZenith Monday 09:35
The example above shows how it operates with a radiator
system. Radiator system 1 without a room sensor.
The example above shows how it operates with a radiator
system and cooling.
1 2
Dansk Nederlands Čeština
Svenska Norsk English
Eesti Polski Slovenščina
Deutsch Suomi Française
Operation data system
Define Cooling
Cooling No
Common heating/cooling No
Condense pipe secured No
Room temp. cooling 25.0
Def heating circuit 1
Heating circuit 1 Yes
Room sensor 1 Yes
Type Wire
Def heating circuit 1
Heating circuit 1 Yes
Room sensor 1 Yes
Type Wireless
Action
Disconnect
Status
Associated
Level of signal
Battery 85%
Version x0102
Def CTC SMS
Activate Yes
Level of signal
Phone Number 1 +46712345678
Phone Number 2 -----------------
Hardware Version 1 1
Software Version 1 9
Pump H-tank (G46) Off
Temperatures
H-tank (B6) ºC 32
Test Diff thermostat function
Charge start diff temp ºC
7
Charge stop diff temp ºC
3
Charge temperature °C 60
Sett. Diff termostat function
Holiday
Cooling 20.2 (20.0)
Heating circuit 1 20.2 (20.0)
Room temp.
Night reduction
Op. Heating Circuit
Primary flow1 ºC 33(34)
Return flow ºC 31
Radiator pump Till
Mixing valve Open
Delay mixing valve 180
Primary flow 2ºC 33(34)
Radiator pump 2 Från
Mixing valve 2
Settings language
Settings language