User guide

BB2-7040 User Guide – Rev. 1.2 Page 32
9 Data Objects
The source of data for an Analog Input object will be reading an object in another BACnet device, or receiving of data
from a ZigBee device. The device link will point to a BACnet client read map or a ZigBee client read map.
Out of Service means any polling of the slave device will stop. While out of service, the present value may be written by
the BACnet client. Data may be forced via this web page at any time, but will be overwritten by the next poll unless the
object is out of service.
Reliability codes may be any of the following:
BACnet device timeout (82)
BACnet error returned by server/slave BACnet device (83)
ZigBee device timeout (84)
ZigBee device error (85)
ZigBee reported invalid command (86)
ZigBee reported invalid parameter (87)
Other (99)