BB2-7030 User Guide – Rev. 1.0 Page 66
Reliability (103) BACnetReliability
ENUMERATED: normal(0)
Vendor specific:
no response (64)
crc error (65)
exception, illegal function code (66)
exception, illegal data address (67)
exception, illegal data value (68)
exception, code+65, rarely used (69..79)
configuration property fault (80)
exception, code not recognized (81)
BACnet client read/write timeout (82)
BACnet client received error response from slave (83)
Out_Of_Service (81) (W) BOOLEAN
COV_Increment (22) (W) REAL (analog objects only)
COV_Period (180) (W) Unsigned
Priority_Array (87) BACnetPriorityArray (commandable objects only)
SEQUENCE SIZE (16) OF BACnetPriorityValue
REAL (each element, analog output objects)
ENUMERATED (each element, binary output objects)
Unsigned (each element, multi-state output objects)
Relinquish_Default (104) (W) REAL (analog objects)
ENUMERATED (binary objects)
Unsigned (multi-state objets)
Polarity (84) BACnetPolarity (binary objects only)
ENUMERATED: normal(0)
Number_Of_States (74) Unsigned (multi-state objects only)
Units (117) BACnetEngineeringUnits (analog objects only)
19.2 Device Object Properties
The following properties are found in the Device object of the BB2-7030. In addition to standard
Device properties, configuration properties that apply at a system level to the whole device are
included here.
Property Encoding
Object_Identifier (75) BACnetObjectIdentifier