Specifications
18
PROGRAMMING THE TIMER
Note: The PLC uses military time – all times must be programmed in that format.
1. From the STS 7004 Home Screen, touch the “AUTO TIMER CONFIG” screen to navigate to the Auto
Pump Timer Configuration Screen.
2. Touch the day button to select the day of the week you want the Auto Timer to run.
3. Touch the time values to set the Pump Start and Stop times in Auto (use 24hr time format.)
4. Up to three separate timers can be set for each day of the week.
5. Touch the “Menu” button to return to the STS 7004 Home Screen.
Please call AXI International with any questions.
FUEL LINE LEAK
If fuel is detected in the spill / drip tray, the float switch will activate the fuel leak alarm, illuminating the
“LEAK DETECTION” indicator. The pump motor will shut off and remain locked out of operation until the
leak has been corrected and the “ALARM RESET” button has been pushed. Before removing the spilled
fuel from the basin, turn the key switch to the “OFF” position. Always make sure to find the cause of the
leakage and correct it. After removing the spilled fuel, allowing the leak switch to return to its normal
position, the key switch can be returned to the “AUTO” or “RUN” mode.
Note: Disposal of fuel and associated waste should be done in accordance with Federal, State
and Local regulations.
STABILIZING AND OPTIMIZING FUEL QUALITY
We recommend treating the fuel with the AXI INTERNATIONAL Fuel Catalyst (AFC-705). This will
enhance and accelerate the tank cleaning process by breaking down and dissolving existing tank sludge.
AFC-705 will decontaminate compartments of the tank that are out of reach of the suction line.