Interlock
- Interlock Required / With / Delay: With
"Interlock Required", all users will be denied access
until all of the (up to 3) other doors selected here
have been closed (and relocked) for the selected
"Delay" time-period.
Tip: This allows limiting the number of persons who
can enter in close proximity, and/or the speed at which
persons can enter a specific area.
Special
- Detect Wandering Patient: Select this for
an exterior door, or other area of concern where
unauthorized (and/or infirm) patients are to be
detected.
With this application, user 'access tokens' will typically
be a wireless wristband (with appropriate detection in
the door frame).
When a 'wandering patient' approaches, an alarm will
be triggered, and the door can optionally lock as they
approach (see next setting). As well, hospital staff can
be given the authority to cancel the alarm by
presenting their (applicable/compatible) token at this
door.
To assign 'wandering patient' status, or provide the
authority to reset associated door alarms, refer to the
"Special Attributes" selections under "Authorities for
Users/Entrants".
- Lock Door on wandering patient Detected:
With the "Detect Wandering Patient" selection,
this causes the door to lock when a 'Wandering
Patient' is detected. (See the preceding setting,
notes, and references.)
- In/Out Station: This applies to a reader being
used to log cardholder arrivals and departures
(e.g., a time-clock application)
.
With this feature, the reader will not be associated with
an access-controlled door.
- Turnstile: Select this for a turnstile that is being
used with anti-passback and 'escort-required'
users. (APB will be ignored for the escort--
allowing them to badge again to gain entry.)
Related: In Reader "Detect Antipassback",
previous/above; Account Information Setup
"Escort-Required Mode"; Authorities "Escort
Privilege", and "Visitor (Escort Required)".
- Do not Lock on Door Closure: Future Use.
The door will not relock until the 'momentary
unlock' time expires.
- Force Buzzer Clears on Door Closure: Future
Use.
- Insertion Reader: Future Use.
About Video Events
.
Video events are specific events pertaining to
input points and doors that have been
associated with recordings from one or two
specific camera(s). These appear with a
camera symbol on the left in the event
monitoring window.
Clicking the camera symbol allows viewing the
recording for that camera at the time of the
event. If a video that coincides with the event
is available, it will open and start playing
automatically starting at the time of the
triggering event
Note: Playback for video events is NOT supported for
March R4 DVRs.
Video Events
Note: This tab will appear only if at least one camera is
presently defined.
Also See: Setting up Video Events".
First Camera
- Select Camera: This allows selecting the first
(or only) camera to be associated with specific
events from this door.
- Alarm / Granted / Denied: Allows selecting the
type of events from this door that will be
associated with the selected camera.
Second Camera
- Select Camera: This allows selecting a second
camera to be associated with specific events
from this door. This allows for a second
camera-angle for video-events pertaining to this
door.
- Alarm / Granted / Denied: Allows selecting the
type of events from this door that will be
associated with the second camera.
Elevators (Lifts) and
Associated Readers
If you change any
value for an elevator/lift, this will
cause that device to be reset to its default / scheduled
state (this allows configuration updates to be managed