4 - 505 SoftShop Setup 505 SoftShop for Simatic 505
Figure 4.3
2. Select the appropriate setting for each option in the dialog box.
Serial Port: Location where the serial communication port
(COM1, COM2, COM3, or COM4) is configured for
communications. You do not select which port to
communicate out of at this stage.
Response T.O. (sec): Specifies the amount of time, in
seconds, that the software waits for a response from the
PLC before returning a time-out error. Any whole number
between 5 and 25 can be used.
Retries specifies Specifies the number of times the software
will try to re-establish communications with the PLC after a
time-out error. Any whole number between 0 and 10 can be
used. Use 0 for no retries.
Dial Modem: Selected when the selected form of serial
communications is through a modem. The modem
parameters must be set to exactly the same communication
parameters that you will use. Use the following modem
parameters: eight bits, no parity, one-stop bit, and the
highest baud rate that your equipment will support.
Baud Rate: The rate of communications between the
computer and modem.
Telephone Dialing: Specifies which type of dialing to use.
Specify pulse dialing only if this is the only type your phone
line supports.
Force NITP: Specifies ASCII communications for the 545,
555, and 575.
Initialization Command: The initialization commands sent
to the modem. Consult your modem manual for a list of
appropriate commands.