8553N136
- open the sweeping door (upper door) by unscrewing the 4 lock nuts.
- remove the convection baffles,
- using the brush supplied, carefully sweep the 6 flue sections,
- also brush the convection baffles and the front face,
- if possible use a vacuum cleaner,
- put the convection accelerators back in place (pay attention to their
direction),
- shut the door.
Maintenance of the combustion chamber
- open the combustion chamber door (lower door) by unscrewing the
4 lock nuts
- brush the inside of the combustion chamber
- using a vacuum cleaner, vacuum up the soot deposits which have
accumulated in the combustion chamber
- close the door and replace the front cover
1 : stop pins
2 : brush
3 : vacuum cleaner brush
4 : vacuum cleaner
Cleaning the smoke box (Flue Hood)
For this purpose :
-remove the sweeping left and right hand covers of the smoke box (2
wing nuts) and remove the soot which has accumulated using a
vacuum cleaner
-replace the sweeping covers.
Burner maintenance :
In accordance with the directions supplied with the burner.
Baffle Position Baffle Fraction mm GT 304 A/II GT 305 A/II GT 306 A/II GT 307 A/II GT 308 A/II GT 309 A/II
Upper [3rd Pass]
8219-0017 16 1/4 410
088400
Middle [2nd Pass]
8219-0018 22 7/16 570
400488
8219-0019 16 1/4 412 222242
8219-0020 22 1/2 572 000002
Lower
[1st Pass]
21