Specifications
Technology Upgrade Security Recording 28 3600-4
1224_01
1) Hard drives shall be configured with 15000 RPM drives recording for
immediate recording of images.
2) Slower drives can be used for long term storage.
9. NVR shall allow connection to a permanent backup device.
10. Each NVR shall have dual power supplies.
11. The NVR shall have Two Gigabit Ethernet connection(s) via an RJ-45 type interface.
12. The NVR systems shall allow offloading of recorded images via an on-board CD/DVD
writer.
13. The NVR shall be 19 inches rack mountable.
a. Where multiple servers are provided the contractor shall provide a KVM switch
and rack mounted LCD and keyboard.
b. Provide one, (1), TRIPP LITE #B020-008-17
14. The NVR Servers shall be supplied with no less than three years of 24x7
maintenance that includes next day replacement of drives and service on the server.
15. Servers shall be from the following manufacturers
a. Hewlett Packard
b. Dell
16. Remote viewing for mobile devices.
a. Provide a server or processing power in the main servers to support remote
viewing of camera images on smartphones or tablet devices.
B. The Security Monitoring PC shall meet the following requirements: (These
1. Operating system shall be Windows® 7/8
2. Processor shall be no less than 3.4 Ghz, I7-2600 processor. Intel or AMD. 64 bit
3. Shall be equipped with memory of 8 GB.
4. Equip each unit with a hard drive of no less than 200GB.
5. Each PC shall have an integrated high speed Video/graphics card capable of no less
than 2 separate video monitor outputs.(DVI,HDMI or VGA) Include multiple video
cards if required.
a. Minimum 1 GB memory
6. The optical drive shall be no less than a 16X/48X DVD-ROM reader/writer drive
7. Equip each with an Ethernet controller with 10/100/1000 Mbit connectivity
8. Equip each with a keyboard and wireless four button optical scroll mouse.
9. Provide a minimum of two additional USB connections with at least one USB on the
front of the unit.
10. Each PC shall be equipped with Two (2), 24”, 16x9 aspect ratio, diagonally measured
LCD monitor.
2.03 UPS SYSTEM
A. Contractor shall provide a UPS system that will serve the server and Ethernet switch that
attach to the server switch in the main communications room.
B. The rack mount UPS shall be sized to provide 25 percent growth/overhead from the switch to
which it is connected.
C. Input shall be:
1. 120V AC
2. Input Frequency: 50/60 Hz +/- 3 Hz (auto sensing).
3. Input Connections: NEMA 5-15P.
4. Cord Length: 6 feet (1.83 meters).
5. Input voltage range for main operations 82 - 144V.
D. Output:
1. Nominal Output Voltage: 120V.
2. Output Voltage Distortion: Less than 5 percent at full load.
3. Output Frequency: (sync to mains) 47 - 53 Hz for 50 Hz nominal, 57 - 63 Hz for 60 Hz
nominal.
4. Crest Factor: Up to 5:1.
5. Waveform Type: Sine wave.
6. Output Connections: NEMA 5-15R.