Specifications

Technology Upgrade Access Control 28 3500-18
1224_01
product. Fill in the space with mineral wool, and then install the firestop on top. All
firestop shall be of sufficient thickness to secure the rating required by code.
3. After final cable installation, install a putty firestop around all cables where they enter
and exit conduit pass thru’s and conduit risers.
4. All firestop shall be installed to provide the fire rating as described by local fire code.
5. It shall be the responsibility of the Contractor to verify that all conduits, walls, and
raceways required to be firestopped have been firestopped.
K. Motion Request to Exit devices:
1. Where shown on the drawings install a passive infrared motion based request to exit
device.
2. Associate this with one or more doors so that when it senses motion it shunts the door
contact.
3. Wire this back to the panels in the comm. rooms.
4. Install above the door.
L. Power Supplies at Doors:
1. The power supply is located above the door to power the electric latches, latch
retractors.
2. Connect the power supply to the latch retraction device.
3. Wire from the power supply back to the panels in the comm. rooms.
M. Assisted Opener
1. Where an assisted opener is shown the contractor shall wire to this opener to work:
2. Operation sequence when the doors are locked entering from outside -valid id card
a. If the person presents a valid card then the latch shall retract inside the
exterior door.
b. The latch bolt monitor shall note that the latch is retracted and shall
communicate that information to the control board in the auto opener.
c. The control board shall allow the exterior push button to be energized. Once
the push button is energized then the exterior door shall be opened of the
button is pushed.
d. The exterior auto opener control board shall communicate to the control board
of the interior door and that door shall open.
3. Operation sequence when the doors are unlocked entering from outside
a. The latch bolt monitor shall note that the latch is retracted and shall
communicate that information to the control board in the auto opener.
b. The control board shall allow the exterior push button to be energized. Once
the push button is energized then the exterior door shall be opened of the
button is pushed.
c. The exterior auto opener control board shall communicate to the control board
of the interior door and that door shall open.
4. Operation sequence when the doors are locked entering from outside -no card or
invalid card
a. If the person pushes the exterior opener button then the auto opener shall not
engage because the opener button is not energized.
b. The exterior opener button is not energized unless the latch bolt monitor notes
that the latch is retracted.
5. Operation sequence when the doors are locked, exiting from interior
a. When a person pushes the interior opener button then that shall communicate
with the interior auto opener and open that door.
b. The control board of the interior auto opener shall communicate with the
control board of the exterior auto opener and note that the interior opener
button has been pressed.
c. The control board of the exterior auto opener shall communicate with the
access control system and instruct it to retract the latch on the exterior door.
d. The exterior control board shall wait a set number of seconds and then it shall
engage the exterior auto opener to open the exterior door.
6. Operation sequence when the doors are locked, exiting from vestibule