Specifications
Technology Upgrade Access Control 28 3500-17
1224_01
F) Alarm level setting for different doors based on time of day and day ofw
week.
G) Lockdown and Normal locking schedules. Configure the system to lock
all doors upon going into lockdown mode through the button or through
the software system.
H) Setup all user logins to allow specific viewing of portions of the system
based on login ID.
d. Set all alarm levels and outgoing calling attributes such as central station
outcalls, paging and email alerts.
A) Add users and all those that are to be notified on a building basis.
B) Set levels for all door contacts such that the owner is notified of a door
open when the system is armed but is not alerted during the day unless
they ask for this type of configuration.
e. Generate customized maps for each building.
A) Create maps from the owner that have multiple levels such as entire
building and then subdivided into different areas.
B) The maps shall show icons for each door. The icons shall be green or
red based on open or closed door.
C) Setup all icons to allow the owner to click on a door and then have
direct access to lock or unlock or pulse the lock on a door.
f. Setup all user accounts and install the user software on the owners pc’s.
A) Setup the user accounts based on the doors or buildings they will be
allowed to control.
B) Work with the owner to determine which panels, doors, maps or
buildings the user will be able to see and control.
G. Door Contacts:
1. Install door contacts where shown on the drawings.
2. Work with door provider and installer on timing of door contact installation.
3. Install raceways to allow installation of the door contacts.
4. Drill into the door frame and door to allow installation of the door contact and the
associated cable. No cable shall be visible after installation.
5. Where door frames are filled they shall be drilled out to allow installation of the door
contact. Surface mount contacts are not allowed at any student accessible doors.
H. Card Readers:
1. Card readers shall be installed at locations shown on the drawings.
2. Coordinate installation of all card readers with the doors and walls.
3. Where the reader is mounted on the door, coordinate the installation with the
installation of the door to allow all cable for security/access.
4. Locate all card readers at ADA compliant heights and locations.
5. At the garage doors the card readers shall be installed in a weatherproof method and
shall be weatherproof.
6. The long range reader shall be installed to the wall and secured with a custom mount.
7. Contractor shall install and test one of the card in a car to test the system to allow it to
open the garage door.
I. Electric Latch/Latch Retraction device.
1. The Electric Latch shall be installed by the door hardware contractor.
2. Work with the Electrical Contractor and others to integrate the security system to the
latch retractors and their door controllers.
3. Install all cables required to be connect this device to the security system and power
supply.
J. Firestopping is required at all riser conduits, and all pass thru’s.
1. Each cable tray penetration of a wall shall be firestopped after cable installation. Use
pillow type firestop to allow additional cables to be installed in the future.
2. Where riser conduits pass through floors, the area between the concrete and the
conduit shall be firestopped. This shall be completed with a putty or liquid firestop