1. NFPA 70, Type CMP.
2. Flame Resistance: NFPA 262 Flame Test.
K. Plenum-Type, Multiconductor, Readers and Keypads Cable: 6 conductors, No. 20 AWG,
stranded (7x28) tinned copper conductors, fluorinated-ethylene-propylene insulation, overall
aluminum foil-polyester tape shield with 100 percent shield coverage plus tinned copper
braid shield with 85 percent shield coverage, and fluorinated-ethylene-propylene jacket.
1. NFPA 70, Type CMP.
2. Flame Resistance: NFPA 262 Flame Test.
L. Paired Lock Cable: 1 pair, twisted, No. 16 AWG, stranded (19x29) tinned copper
conductors, PVC insulation, unshielded, and PVC jacket.
1. NFPA 70, Type CMG.
2. Flame Resistance: UL 1581 Vertical Tray.
M. Plenum-Type, Paired Lock Cable: 1 pair, twisted, No. 16 AWG, stranded (19x29) tinned
copper conductors, PVC insulation, unshielded, and PVC jacket.
1. NFPA 70, Type CMP.
2. Flame Resistance: NFPA 262 Flame Test.
N. Paired Lock Cable: 1 pair, twisted, No. 18 AWG, stranded (19x30) tinned copper
conductors, PVC insulation, unshielded, and PVC jacket.
1. NFPA 70, Type CMG.
2. Flame Resistance: UL 1581 Vertical Tray.
O. Plenum-Type, Paired Lock Cable: 1 pair, twisted, No. 18 AWG, stranded (19x30) tinned
copper conductors, fluorinated-ethylene-propylene insulation, unshielded, and plastic jacket.
1. NFPA 70, Type CMP.
2. Flame Resistance: NFPA 262 Flame Test.
P. Paired Input Cable: 1 pair, twisted, No. 22 AWG, stranded (7x30) tinned copper conductors,
polypropylene insulation, overall aluminum foil-polyester tape shield with No. 22 AWG,
stranded (7x30) tinned copper drain wire, 100 percent shield coverage, and PVC jacket.
1. NFPA 70, Type CMR.
2. Flame Resistance: UL 1666 Riser Flame Test.
Q. Plenum-Type, Paired Input Cable: 1 pair, twisted, No. 22 AWG, stranded (7x30) tinned
copper conductors, fluorinated-ethylene-propylene insulation, aluminum foil-polyester tape
shield (foil side out), with No. 22 AWG drain wire, 100 percent shield coverage, and plastic
jacket.
1. NFPA 70, Type CMP.
2. Flame Resistance: NFPA 262 Flame Test.
R. Paired AC Transformer Cable: 1 pair, twisted, No. 18 AWG, stranded (7x26) tinned copper
conductors, PVC insulation, unshielded, and PVC jacket.
1. NFPA 70, Type CMG.
S. Plenum-Type, Paired AC Transformer Cable: 1 pair, twisted, No. 18 AWG, stranded (19x30)
tinned copper conductors, fluorinated-ethylene-propylene insulation, unshielded, and plastic
jacket.
1. NFPA 70, Type CMP.
2. Flame Resistance: NFPA 262 Flame Test.
T. Elevator Travel Cable: Steel center core, with shielded, twisted pairs, No. 20 AWG
conductor size.
1. Steel Center Core Support: Preformed, flexible, low-torsion, zinc-coated, steel wire
rope; insulated with 60 deg C flame-resistant PVC and covered with a nylon or cotton
braid.
Shielded Pairs: Insulated copper conductors; color-coded, insulated with 60 deg C
flame-resistant PVC; each pair shielded with bare copper braid for 85 percent
coverage.
a. Jute Filler: Electrical grade, dry.
b. Binder: Helically wound synthetic fiber.
c. Braid: Rayon or cotton braid applied with 95 percent coverage.
d. Jacket: 60 deg C PVC specifically compounded for flexibility and abrasion
resistance. UL VW-1 and CSA FT1 flame rated.