Specifications

Technology Upgrade Cat-6 Cabling 28 1600-4
1224_01
11. Jacks shall terminate 22-26 AWG stranded or solid conductors.
12. Jacks shall terminate insulated conductors with outside diameters up to .050 inches.
13. Jacks shall be compatible with single conductor, 110 impact termination tools.
14. Jacks shall include translucent wire retention stuffer cap that holds terminated wires
in place and allows the conductors to be visually inspected in the IDC housing.
15. Jacks shall be compatible with EIA/TIA 606A color code labeling.
16. Jacks shall accept snap on icons for identification or designation of applications.
17. Jacks shall be marked for T568A and T568B wiring schemes. TIA 568B wiring shall
be used in all terminations throughout the communications system.
18. All CAT-6 modular jacks and panels shall meet or exceed the following transmission
characteristics:
a. Jacks shall be designed for 100 Ohm UTP cable termination.
b. Jacks shall be UL verified for TIA/EIA Category 6 electrical performance.
c. Jacks shall be UL listed 1863 and CSA certified.
d. Jacks shall be manufactured by an ISO 9002 registered manufacturer.
19. CAT-6, 8-pin modular jacks shall be:
a. Data Jacks shall be Hubbell # HXJ6OW or equal. Office White.
b. Data Jacks for Security Cameras shall be Hubbell #HXJ6GN-Green
c. Data jacks for Wireless Access Points shall be Hubbell #HXJ6Y-Yellow
d. Other jacks shall be as described on the drawing and shall be colored to
match the cabling where noted for AV equipment.
C. Provide surface mount boxes for termination of cables as shown on the drawings.
1. Install a surface mount box at location for termination of the CAT-6 jack.
2. Single cable surface box shall be Hubbell #ISM1OW.
3. Multiple cable surface box shall be Hubbell #ISM20W.
D. Standard flush mount faceplates shall support all the jacks and connectors required.
1. Faceplates shall be UL listed and CSA certified.
2. Faceplates shall be constructed of high impact thermoplastic.
3. Faceplates shall be 2-3/4 inches wide x 4-1/2 inches high (69.8 mm x 114.3 mm) for
single gang, and 4-1/2 inches x 4-1/2 inches (114.3 x 114.3 mm) for double gang.
4. Faceplates shall be available to mount 1, 2, 3, 4, or 6 jacks in a single gang and up to
12 jacks in a double gang configuration.
5. Faceplates shall provide for TIA/EIA 606A compliant station labeling.
6. Faceplates shall have plastic covers over the mounting screws that can be replaced
with a clear plastic window over a printable paper insert.
7. Each plate shall be fully configured with modular inserts. There shall be no open
spaces in the faceplate.
8. Match the color of the modular inserts to the color of the faceplate. All faceplates and
inserts shall be office white unless otherwise noted.
9. Single gang faceplate shall be Hubbell # IMF1OW.
10. Double gang plate shall be Hubbell # IMF2OW.
11. Double Gang, stainless steel, modular faceplates shall be Hubbell #IMS2
12. Each single gang plate has 3 faceplate units (FPU’s) available to install inserts.
Double gang plates have 2 sides, each with 3 FPU’s.
13. Equip plates with the following parts as directed on the construction drawings.
FPU
ITEM
PART NUMBER
Blank Jack
SFB10
.5
Blank
IMB05OW
1
Blank
IMB1OW
1.5
Blank
IMB15OW
1
1 Port Flat
IM1K1OW
1
2 Port Flat
IM2K1OW
1.5
1 Port Angled
IM1KA15OW
1.5
2 Port Angled
IM2KA15OW