Specifications
Technology Upgrade Fiber Cabling 28 1500-2
1224_01
10. The fiber optic cable shall meet or exceed the requirements of this specification when
measured in accordance with the methods of the individual requirements or the
following methods as defined in EIA-STD-RS-455.
a. Fiber dimensions.
b. Attenuation.
c. Bandwidth.
d. Numerical aperture.
e. Fiber proof test.
f. Cable bending.
g. Tensile load
h. Impact resistance.
i. Crush resistance.
j. Attenuation vs. temperature.
11. Manufacturer shall provide ISO 9001 certification.
12. The cable shall withstand an impact force 1500 times per ANSI/TIA/EIA-RS-455
(FOTP-25A).
13. The cable shall withstand compression load of 1800 N/cm per ANSI/TIA/EIA-RS-455
(FOTP-41A).
14. Fiber shall be indoor/outdoor rated based on the areas in which the fibers will be
installed. Do not install riser rated fiber through a plenum rated area unless the fiber
is inside an EMT conduit.
B. Indoor Rated type fiber shall be. Optical Cable Corporation DX series fiber cables or equal.
1. The multi-fiber cables shall consist of tight buffered optical fibers surrounded by a
synthetic yarn strength member and a color coded flame retardant elastomeric
polymer jacket. The strength member shall be composed of individually and precisely
tensioned elements such that tensile loads are equally shared by each element.
2. 12 strand multi-mode plenum rated fiber cable shall be Optical Cable
#DX012SALT9QP Aqua in color. OM3 fiber cable.
a. Wavelength: 850/1310nm
b. Industry Standard: OM3
c. 1 Gigabit Ethernet Distance: 750/600 meters
d. 10 Gigabit Ethernet Distance: 150/300 meters
e. Max Attenuation: 3.0/1.0 dB/km
f. Laser Bandwidth: 950/500 MHz-km
3. 12 strand single-mode plenum rated fiber cable shall be Optical Cable
#DX012SSLX9YP yellow in color.
a. Wavelength: 1310/1550nm
b. Industry Standard: ITU-T G.652.D
c. 1 Gigabit Ethernet Distance: 5 km
d. 10 Gigabit Ethernet Distance: 10 km
e. Max Attenuation: .5/.5 dB/km
C. 12-36 port, rack mount fiber patch panels shall be Hubbell # FPR3SP or equal.
1. Rack mount fiber patch panels shall be modular in design. Mounting brackets shall
be provided for 12 pack adapters. Adapter packs shall sit horizontally in the panel.
2. Panels shall mount into standard 19 inch relay racks.
3. Panels shall be no more than 1-3/4 inch or 1 rack unit high.
4. Each panel shall be equipped with a protective front cover bracket, Hubbell No.
FPRBRKT1.
D. 12-36 port, wall mount fiber patch panels shall be Hubbell # FPR3SP or equal.
1. Rack mount fiber patch panels shall be modular in design. Mounting brackets shall
be provided for 12 pack adapters. Adapter packs shall sit horizontally in the panel.
2. Panels shall mount into the wall.
3. Fiber panel shall be Hubbell #FCW4SP or equal. Equip with all SC adapter panels.
E. 12-pack adapter panels shall be installed in each fiber panel for termination.
1. Adapters shall support 12 fibers each.