Specifications

Technology Upgrade Communications Grounding 28 1150-3
1224_01
D. Terminate and connect all ground cables with crimp type connectors.
1. Use star washers on all connections of ground cables to ground bars and racks and
equipment.
E. Ground systems shall be tested after installation to ensure proper installation and
connectivity.
1. Test procedures shall be fully spelled out. They shall minimally include, the time and
date of the test, name of tester, device used to test ground potential, and test results.
2. The Contractor shall provide test results, to the Engineer for final approval and sign
off.
3. Ground connections shall be tested at each rack in each communications room. The
system shall not be considered complete until the ground tests have been completed
and acceptable results are provided.
END OF SECTION