Specifications
Technology Upgrade Communications Room 28 1100-2
1224_01
Figure 28 1100-A – Isometric View of Communications Racks
C. Patch Cord Organizers:
1. Patch cords organizers shall be steel and shall allow routing of patch cables from
electronics to the patch panels.
2. Single rack unit organizer shall be Hubbell No. HC119ME3N with hinged cover,
Hubbell No. HC119C. Refer to PCO-1 on detailed drawings.
3. 2 rack unit organizer shall be Hubbell No. HC219ME3N with hinged cover. Refer to
PCO-2 on detailed drawings.
4. When multiple racks are provided in a row, the Contractor shall provide 1 Hubbell No.
HC219MS1N per rack for use as an interbay organizer.
5. Approved equals, Ortronics and Great Lakes Case and Cabinet.
D. Hook and Loop Wraps:
1. Hook and Loop wraps shall be used on the cable ladder of the rack systems to bundle
the cables as they pass along the cable ladder. Cables shall be bundled in groups of
no more than 24 cables.
2. Hook and Loop wraps should not be used above the drop ceiling or in cable tray
except in limited circumstances. The pathway shall support the cables without the use
of extra tie wraps.
3. Wraps shall never be used to support cables from building structure, electrical
conduits, or lighting systems.
4. Panduit No. PLT2S-C702 or equal plenum rated tie wrap. Use only this type of tie
wrap in plenum rated areas.
5. Panduit No. PLT2H-L00 or equal ultraviolet rated outside plant tie wrap. Use only this
type of tie wrap for outside uses.
E. Power Strips:
1. Raceway and all components shall be UL listed. The base and cover shall be ivory in
color, and shall be attached to the cable ladder of the rack system.