Technical data

INSTALLATION REQUIREMENTS
5”(125mm) FLUE PIPE AND STARTER BOX
A DOUBLE WALLED SELKIRK RECESSED FLUE BOX BUILT TO THE
REQUIRMENTS OF BS 715 WITH AN INSULATED FLUE HAVING A
MINIMUM DIAMETER OF 125mm(5”) AND A MINIMUM EFFECTIVE
OVERALL HEIGHT OF 3 METRES (10FT)
457mm
610mm
c
560mm
143mm
330mm
407mm
330mm
RECESSED GAS FLUE BOX DIMENSIONS(NOT INCLUDING FIBREGLASS
INSULATION)
NOTE
THE METAL FLUE BOX MUST BE INSULATED WITH FIBREGLASS OR
EQUIVALENT TO A THICKNESS OF 25mm
NOTE
WHERE INSTALLATION IS FOR A METAL FLUEBOX.THE SURROUND
MUST HAVE A TEMPERATURE RATING OF 150 DEGREES C
NOTE
IF A FLUE BOX IS TO BE USED WITH A EXISTING BRICK OR STONE
CHIMNEY A 125mm MINIMUM DIAMETER FLUE LINER CONFORMING TO
BS 715 CAN BE USED
NOTE
A BRICK CHAMBER TO THE SIZES IN FIG 2 .IN AN EXISTING BRICK OR
STONE CHIMNEY A 125mm (5”) MINIMUM DIAMETER FLUE LINER
CONFORMING TO BS 715 MAY BE USED,PROVIDING THAT IT IS SEALED
AT THE TOP AND BOTTOM OF EXISTING BRICK OR STONE CHIMNEY.
NOTE
ANY OF THE ABOVE FLUES MUST NOT BE RESTRICTED BY DAMPERS
OR REGISTER PLATES.THE FLUEMUST SERVE ONLY ONE APPLIANCE
AND NOT HAVE ANY BRANCHES OR TRAPS WHICH MAY IMPEDE THE
NATURAL DRAUGHT .IF ANY TERMINAL IS FITTED IT MUST BE
SUITABLE FOR THE PURPOSE
ISSUE 2
7