Technical data
ISSUE 2 
11
TEST FOR SPILLAGE 
CHECK FOR SATISFACTORY CLEARANCE OF COMBUSTION PRODUCTS 
CLOSE ALL DOORS AND WINDOWS IN THE ROOMS CONTAINING THE 
FIRE. 
TURN ON GAS FIRE AND SET THE CONTROL TO HIGH 
LEAVE THE FIRE BURNING FOR FIVE MINUTES AND INSERT A LIGHTED 
SMOKE MATCH ON A VERTICAL PLANE 
50 mm DIRECTLY UNDER FRONT EDGE OF CANOPY AND 50mm FROM 
EITHER SIDE OF THE OPENING 
ALL SMOKE MUST BE DRAWN INTO THE FLUE 
IF SPILLAGE OCCURS ALLOW A FURTHER TEN MINUTES 
SHOULD SPILLAGE STILL OCCUR TURN OFF THE FIRE AND SEEK 
EXPERT ADVICE 
IF AN EXTRACTOR FAN IS SITUATED IN THE ROOM , THIS TEST SHOULD 
BE REPEATED WITH THE FAN RUNNING 
IF THERE IS A ROOM WITH AN EXTRACTOR FAN, THE TEST SHOULD BE 
REPEATED WITH ALL THE DOORS TO THAT ROOM OPENED AND THE 
EXTRACTOR FAN RUNNING 
FITTING TRIMS 
FIT THE TRIM WITH FOUR MAGNETS PLACED ON THE VERTICAL SIDE FLANGES 
OF THE FIREBOX (ONE AT THE TOP AND ONE AT THE BOTTOM) 
OFFER THE TRIM UP AND PUSH INTO POSITION 
PLACE FRET CENTRALLY IN FRONT TO COVER THE CONTROLS 
INSTRUCT USER 
DEMONSTRATE THE LIGHTING AND EXTINGUISHING PROCEDURES TO THE USER 
AND REMOVAL AND REFITTING OF THE TRIM FOR CLEANING. 
THE APPLIANCE SHOULD BE OPERATED WITH THE GAS CONTROL NOT TURNED ON 
MORE THAN LOW FOR THE FIRST FIVE HOURS OF USE TO ALLOW THE FIBRE 
FUEL TO CURE SLOWLY. 
THE CURING EFFECT OF HEATING THE FUEL AND OTHER CERAMICS COMPONENTS 
WILL CAUSE AN INITIAL ODOR. 
THE APPLIANCE SHOULD BE SERVICED ANNUALLY BY A COMPETENT PERSON IN 
ACCORDANCE WITH THESE INSTRUCTIONS AND THE APPLIANCE CHECKED FOR 
SPILLAGE IN ACCORDANCE WITH THE METHOD DETAILED IN THESE 
INSTRUCTIONS 
HAND THESE INSTRUCTIONS TO THE USER. 










