Service manual
Frozen water 
bath
1. 
2. 
3. 
4. 
Bad ice bank control. 
Refrigerant leak causing 
undercharge.
Defective agitator motor.
Dirty water bath.
1. 
 2. 
 3. 
 4. 
Replace bad ice bank control. 
Repair leak, evacuate and re
-
charge.
Replace defective agitator.
Melt ice, empty & clean bath. 
Replenish w/fresh water. 
Cooling or 
condensing unit 
non
- 
operational
1. 
2. 
3. 
4. 
5. 
6. 
7. 
8. 
No electrical power. 
Defective ice bank control.
Dirty condenser unit.
Improper voltage/amperage
Loss of refrigerant.
Bad overload and relay.
Compressor bad.
Restriction (pinched or crimped 
line). 
1. 
2. 
3. 
4. 
5. 
6. 
7. 
8. 
Plug power cord into electrical 
box. Check on/off switch.
Replace ice bank control.
Clean condenser unit w/vacuum 
cleaner.
Check for proper 
voltage/amperage.
Repair leak and replenish 
refrigerant.
Replace overload and relay
Replace compressor.
Repair, straighten or replace 
de
fective line. 
Agitator motor 
not operating 
1. 
2. 
3. 
4. 
Agitator propeller obstructed or 
lost.
Low voltage.
Loose, unplugged, or broken 
wiring.
Bad agitator motor. 
1. 
2. 
3. 
4. 
Remove obstruction or re- 
Attach propeller.
Voltage must be at least 110 volt 
at terminals.
Tighten connection or replace 
broken wiring.
Replace agitator motor. 
Compressor 
does not 
operate
1. 
2. 
3. 
4. 
5. 
6. 
7. 
8. 
No power source. 
Electrical power to cooling unit 
turned off.
Low voltage.
Loose, disconnected, or broken 
wire.
Inoperative ice bank control.
Inoperative overload protector or 
start relay.
Inoperative compressor.
Full ice bank. 
1. 
2. 
3. 
4. 
5. 
6. 
7. 
8. 
Plug power cord to electrical box. 
Check line voltage.
Turn on power switch to unit.
Voltage must be at least 110 V at 
compressor terminals at start. 
Tighten connection or replace 
broken wiring.
Replace ice bank control.
Replace defective part.
Replace compressor.
Refrigeration not called for. 
Compressor 
works 
continuously 
but does not 
form sufficient 
ice bank
1. 
2. 
3. 
4. 
Cooling capacity is exceeded by 
over drawing.
Cooling unit located in 
excessively hot area.
Air circulation through condenser 
coil is restricted
Loss of refrigerant or in
-
sufficient 
charge. 
1. 
2. 
3. 
 4. 
Reduce amount of drinks taken 
per given time of install higher 
volume unit.
Relocate cooling unit.
Check and if necessary, clean 
condenser coil.
Repair leak and/or recharge with 
sufficient refrigerant. 
43 