Datasheet
CN Series Assemblies
Other Crydom products and competitive part number cross-reference available at: www.crydom.com
R024D 24DRA-CN
Series
Load Voltage
024D: 24 VDC, 3.5 A
048D: 48 VDC, 0.1 A
240A: 240 VAC, 2 A
Assembly Input Voltage
05: 05 VDC
24: 24 VDC
120: 120 VAC
240: 240 VAC
Switching Mode
Blank: Zero Cross
Turn-On (AC Output Only)
R: Random Turn-On
(AC Output Only)
Required for valid part number
For options only and not required
for valid part number
Mechanical Dimensions
Tolerances: ± 0.02 in / 0.5 mm
All dimensions are in: inches [millimeters]
Part Number Nomenclature
3.15
[80.0]
3.64
[92.6]
0.24
[6.1]
A1+
14
A2-
(13+)11
DRSCN24
Maximum Socket Rating:
Input: U
N = 24VDC
Output: max. 250V/6A
Plug in Relay Options:
Solid State Relay: CN024D24
CN048D24
CN240A24
SSR Ratings should not exceed socket rating
1411A1+A2-
1413+A1+A2-
DC Output
AC Output
R
NC
Socket Part Number
24 VDC 2A/240VAC
CN240A24
A2- A1+
11 14
R
A1+
11
14
A2-
Wiring Diagram
Control
Load
Line
Supply
A1+
14
A2-
(13+)11
DRSCN24
Maximum Socket Rating:
Input: U
N = 24VDC
Output: max. 250V/6A
Plug in Relay Options:
Solid State Relay: CN024D24
CN048D24
CN240A24
SSR Ratings should not exceed socket rating
1411A1+A2-
1413+A1+A2-
DC Output
AC Output
R
NC
Socket Part Number
24 VDC 2A/240VAC
CN240A24
A2- A1+
11 14
R
A1+
11
14
A2-
Assembly part number is marked on the opposite side of the socket from
the socket's labeling.
The air gap is the clearance distance adjacent to either side of the relay or
assembly measured to the next closer assembly.
For 100 mA output SSRs, no air gap is required for full output current rating.
For sockets intended for AC input control voltage, the AC line can be wired to either
DRS socket terminal A1+ or terminal A2-. Proper polarity must be observed for DC
input control voltage sockets being terminal A1+ positive with respect to terminal
A2-.
For AC loads, the AC line can be wired to either DRS socket terminal 11 or terminal
14. The AC load may also be wired on either the line or neutral side of the SSR. For
DC loads, the proper polarity must be observed for the power supply, load and DRS
socket with terminal 13 being positive with respect to terminal 14.
(I)
Derating Curves
DRA-CN024Dxx
0.0
0.6
1.2
1.8
2.4
3.0
3.5
4.0
0 102030405060
Ambient Temperature (°C)
Load Current (Amperes)
No air gap
Air gap 6.2 mm
(J)
DRA-CN048Dxx
0.00
0.02
0.04
0.06
0.08
0.10
0.12
0102030405060
Ambient Temperature (°C)
Load Current (Amperes)
(K)
No minimum
air gap required
(J)
DRA-CN240Axx
0102030405060
0.0
0.3
0.7
1.0
1.3
1.7
2.0
2.3
Ambient Temperature (°C)
Load Current (Amperes)
No air gap
Air gap 6.2 mm
(J)
(L, M)
(L)
(M)
(K)
(J)
(I)