Datasheet

CTR Series
Ratings 25A per phase @ 600 VAC
DIN-RAIL or Panel Mount 90mm (width) package
• 100K-cycle UL 508 Endurance Rating for Enhanced Reliability
SCR output for heavy industrial loads
• LED input status indicator
AC or DC control
Zero-crossing (resistive loads) or random-fire (inductive loads) output
• UL Reco
g
nized, CE, RoHS and EMC Com
p
lian
t
PRODUCT SELECTION
Description 25 A
4-32 VDC Control CTRD6025
90-140 VAC Control CTRB6025
180-280 VAC Control CTRC6025
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS (1)
Description CTRD6025 CTRB6025 CTRC6025
Operating Voltage (47-63Hz) [VRMS] 48-600 48-600 48-600
Transient Overvoltage [Vpk] 1200 1200 1200
Maximum Load Current (2) [Arms] 25 25 25
Minimum Load Current [Arms] 0.1 0.1 0.1
Maximum Off-State Leakage Current @ Rated Voltage [mArms] 0.25 0.25 0.25
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (3) 500 500 500
Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.35 1.35 1.35
Maximum Surge Current (50/60 Hz, 1 cycle) [Apk] 275/300 275/300 275/300
Maximum I²t for Fusing (50/60 HZ, 1/2 cycle) [A² sec] 380/370 380/370 380/370
HP Rating @ 480V 3 3 3
Minimum Power Factor (with Maximum Load) 0.5 0.5 0.5
Min/Max stranded wire 16/8 AWG 16/8 AWG 16/8 AWG
Min/Max solid wire 16/10 AWG 16/10 AWG 16/10 AWG

Summary of content (5 pages)