Datasheet

Evolution Dual Series
25A & 50A Output rating per channel @ 40°C
120/240 & 480VAC Operating voltage
4-15, 15-32 & 4-32VDC Control input options
Four input termination options
Zero-crossing (resistive loads) or random-fire (inductive loads)
output
Input status LED indicator for each channel
Available with IP20 Touch-Safe” Covers
PRODUCT SELECTION
Control Voltage 240V,25A 240V, 50A 480V, 25A 480V, 50A
4-15 VDC CD2425D1U CD2450D1U
CD4825D1U CD4850D1U
15-32VDC
CD2425E1U CD2450E1U
CD4825E1U CD4850E1U
4-32 VDC
CD2425W1U
CD2450W1U CD4825W1U CD4850W1U
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS (1)
Description Cx2425xxxx Cx2450xxxx Cx4825xxxx Cx4850xxxx
Operating Voltage (47-63Hz) [Vrms] 24-280 24-280 48-600 48-600
Load Current Range (3) [Arms] 0.15-25 0.15-50 0.15-25 0.15-50
Transient Overvoltage [Vpk] 600 600 1200 1200
Maximum Off-State Leakage Current @ Rated Voltage [mArms] 1.0 1.0 1.0 1.0
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (2) 500 500 500 500
Maximum Surge Current 60Hz (16.6ms) [Apk] 300 750 300 750
Maximum Surge Current 50Hz (20ms) [Apk] 275 710 275 710
Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.3 1.3 1.3 1.3
Thermal Resistance Junction to Case (Rjc) [°C/W] 0.65 0.33 0.65 0.33
Maximum I²t for Fusing (8.3 msec) [A² sec] 370 2320 370 2320
Maximum I²t for Fusing (10 msec) [A² sec] 380 2520 380 2520
Minimum Power Factor (with Maximum Load) 0.5 0.5 0.5 0.5

Summary of content (6 pages)