Specifications Sheet
Visit our website at www.crownbattery.com
6CRV390 AGM Deep Cycle Battery
©2017 Crown Battery Manufacturing Company TDS-AGM021200-0817
The battery life reference presented are estimation based upon life cycle testing by the producer. The data references are nominal and should not
be construed as maximum or minimum values for specification or final design. Data for this product type may vary from that shown herein, and
Crown Battery makes no warranties based upon the data shown.
1445 Majestic Drive | P.O. Box 990
Fremont, OH 43420-0990 USA
+1.419.334.7181 | Fax +1.419.334.7124
www.crownbattery.com
commercial@crownbattery.com
The data shown are nominal and should not be construed as maximum or minimum values for specification or final design.
Data for this product type may vary from that shown herein.
Typical battery life is based upon a baseline operating
temperature of 80°F / 27°C. Temperature increases
of 15°F / 10°C over the baseline will cause the
battery’s rate of internal chemical reactions to double
– something that will reduce battery life due to the
accelerated deterioration of internal components.
Please contact Crown Battery to discuss any minimal
requirements for battery life when operating batteries
in temperatures greater than 80°F / 27°C.
Constant Voltage Charging
CYCLE CHARGE: 2.40 - 2.47 V Temperature Correction: +/- 3 mV / °C
FLOAT CHARGE: 2.20 V Recommended Charge Current: 300 Amperes
Maximum Charge Current*: 420 Amperes
CYCLIC CHARGING
Cyclic applications exceeding 50% depth-of-discharge may require different charger voltage set points.
Contact Crown Battery to discuss your application requirements. * Specification requires use of all terminals.
Proper charging of renewable power batteries is essential
to optimize the performance and life of the batteries. To
ensure dependability and life batteries should be charged
after each discharge period. Regular monitoring of battery
voltage condition is recommended to verify system recharging
performance. Refer to the following table for additional charge
control setting information.
Voltage
Setting
O.C.V.
System Voltage
12 Volts 24 Volts 48 Volts
Bulk
2.40 - 2.45 14.4 - 14.7 28.8 - 29.4 57.6 - 58.8
Absorption
2.47 14.8 29.6 59.3
Float
2.20 13.2 26.4 52.8
RENEWABLE POWER CHARGING
DEPTH OF DISCHARGE EFFECT ON CYCLE LIFE
75% DOD
Cycles
End-Cycle
Voltage
50% DOD
Cycles
End-Cycle
Voltage
25% DOD
Cycles
End-Cycle
Voltage
650 1.99 1250 2.04 2500 2.09
Effect of Ambient Temperature
on Battery Life
11.62 (295)
15.91 (404
)
M8
.94 (024)
16
.10 (409)
3.90 (99)
7.01 (178)
8.27 (210)