The data and the user given description is then also available in the PumpLink. OCX utility for use by any
irrigation equipment company’s software.
A print button allowing the user to print setup configurations
Allows the user in one click to cascade or tile all open windows
All screen items will have a help window available to the user
A full pump station owners manual in digital form including graphic images of all touch screens
A database software utility (Maintenance Manager) will be supplied allowing the user to manage and
record all service aspects of his pump station. The utility automatically gets information such as pump
hours and total gallons from Watervision. The database is fully customizable allowing the user to also log
and schedule any other service work completed on ground maintenance equipment or facilities.
Time of use lockout (ability to set up to three unique lockout periods per day of irrigation pumps, water
feature pump, lake fill, and fertigation injection pumps)
Email report notification: Email report can be sent to a specified time each day and or at time of alarm
Audible alarm indication: Upon an active pump station alarm a banner to be displayed on the computer
screen along with an audible alarm noise
Ability to setup fertigation chemical tank diameter and display tank level in gallons
Ability to modify the chemical to station flow ratio without having to manually adjust injection pump
D. Installation of the pump station software shall be seamless to the user. An easy to use
configuration program shall be started by simply inserting the media into the users computer drive
and following the easy to understand instructions.
Watervision, PumpLink, and Maintenance Manager are registered trademarks of Watertronics Inc.
Microsoft, Windows, and Windows NT are registered trademarks of the Microsoft Corporation. Other
brands and product names are trademarks of their respective holder/s.
5.10 PRESSURE TRANSDUCER:
A solid state pressure transducer shall provide a noise free, linear output proportional to discharge
pressure. Transducer shall be solid-state, strain gauge type with integral voltage regulating and output
accuracy not less than 0.25%. Transducer shall be constructed of stainless steel and rated for the
maximum pump station discharge pressure.
5.11 FLOW SENSOR:
The pump station discharge manifold shall incorporate an insertion type, pulse frequency output flow
sensor for continuous output to the pump station controls. The flow sensor output pulse shall be
conditioned and fed directly to the PLC interrupt input for conversion and display in Gallons Per Minute.
For accuracy and security considerations, conversion to an analog signal prior to PLC input shall not be
accepted. Flow sensor accuracy shall be no less than 2% for flow velocities ranging from 1-30 feet per
second.
5.12 LIGHTNING ARRESTER
The main power supply feeding the pumping station shall be equipped with a 3 phase secondary surge
arrester having a breakdown current rating of not less than 80,000 amps. Duty cycle testing: 2500, 10KA
(8x20jus) impulses with less than 10% drift. Sine wave tracking, EMI/RFI noise rejection and <5ns
response time. U.L. category C. approvals 1449 2
nd
addition. Arrester will meet IEEE standard 587.
5.13 SECONDARY CONTROL CIRCUIT FUSES
Single-pole secondary distribution fuses with appropriate ratings shall supply power to each pump starter
coil circuit, the control system and to other circuits as specified.