Specifications

5
monitoring and control purposes. The PLC shall contain two communication ports for monitoring and
programming purposes. The PLC shall contain an EEPROM, battery backed RAM and non-volatile memory for
storage of critical configuration data.
5.7 ALARMS
Controls shall shut down the pump station in the event of the following alarm conditions. The controls shall
attempt to restart the system after alarm shutdown or loss of power to minimize loss of irrigation. After a user
adjustable number of attempts to re-pressurize the system, the controls will go into hard shut down and remain
there until manually reset.
1. Low discharge pressure cutout. Pressure remains 20 PSI below regulated set point for a set
time delay.
2. High discharge pressure cutout. Pressure remains 11 PSI above regulated set point for set
time delay.
3. Phase / voltage cutout; High or low voltage; loss of phase or phase reversal.
4. High pump volute temperature cutout. Pump temperature stays above 120 degrees F. for
a set time delay.
5. Starter fail cutout. Output to starter is not met with corresponding running input for set time
delay. Indicates overload, phase imbalance or control fuse.
5.8 Operator Interface
Operator interface shall be a full color TFT active matrix LCD display unit mounted in the enclosure door.
Operator interface shall be used for logical display of all pump station functions. The operator interface
shall be NEMA 4 rated. The operator interface shall be touch sensitive with intuitive on-screen user
instruction for ease of operator use. The use of buttons or keys or off-screen user instructions shall not be
permitted. The operator interface shall be LCD color display type with no less than 240 x 320 pixel
resolution, with viewing area measuring not less than 5.7" diagonal. User memory for storing critical pump
operation data shall not be less than required for up to 1 year of data.
The operator interface shall allow the user to view and modify all pertinent operation parameters. The
operator interface shall incorporate password protection for modification of critical pump station
parameters. The operator interface capabilities shall include but are not limited to the
following:
a Overview screen showing pump system configuration. Screen shall show if
each individual pump is enable or disabled, the number of hours on each
pump, station full flow and pressure design criteria
b. System screen with information on current regulation pressure, setpoint, regulation
pressure, System status, restarts remaining, VFD reference speed, pressure regulation
method (VFD or EBV modes) and adjust settings button. Adjust settings button will allow
changing parameters etc after entering password.
c. Settings menu to allow changes to pressure regulation settings, pipe
saver mode, VFD manual mode, analog calibration, flow calibration,
program or register settings.
d. Flow screen will display pressure in PSI, flow in GPM and total gallons
pumped in thousands of gallons. Separate display for total gallons pumped
since last reset.