D E S I G N E D T O L E A D Series 32 Gas-Fired Natural Draft Steam or Water Boilers INSTALLATION AND OPERATING INSTRUCTIONS These instructions must be affixed on or adjacent to the boiler. WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury, or loss of life. For assistance or additional information, consult a qualified installer, service agency or the gas supplier. Read these instructions carefully before installing.
Table of Contents I. II. III. IV. V. VI. VII. VIII. IX. X. XI. XII. XIII. XIV. Product Description Specifications Before Installing Locating the Boiler Knockdown Boiler Assembly Instructions Air for Combustion & Ventilation Venting Steam Boiler Piping & Trim Installation A. Heating System Piping B. Indirect Water Heater Piping Water Boiler Piping A. Heating System Piping B. Tankless Heater Piping Gas Piping Control System Wiring A. Standard Steam / Water B.
Figure 1: Base Model - General Configuration II Specifications 42
35 134 5/8 140 1/8 145 1/2 151 156 3/8 161 7/8 167 1/4 172 3/4 32-2185W(S)N 32-2280W(S)N 32-2375W(S)N 32-2470W(S)N 32-2565W(S)N 32-2660W(S)N 32-2755W(S)N 32-2850W(S)N 12 12 12 10 10 12 12 12 12 10 12 12 12 10 12 12 12 10 12 10 12 12 12 10 10 12 'B' Dia. 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 - - - - - - 'D' Dia.
NAT URAL GAS ONLY NUMBER BASIC BOILER OF MODEL SECT IONS I=B=R NET RAT ING INPUT HEAT ING CAPACIT Y (MBH) (MBH) (Sq. ft) (MBH) (MBH) Steam Water WAT ER WAT ER BHP Combustion VOL. 1 VOL. 2 OUT PUT 3 Effy. % (Gal) (Gal) 32-475W(S)N 6 475 380 1188 285 330 80-1/2 28.58 39.80 11.4 32-570W(S)N 7 570 456 1425 342 397 80-1/2 32.65 45.47 13.6 32-665W(S)N 8 665 532 1663 399 463 80-1/2 36.72 51.14 15.9 32-760W(S)N 9 760 608 1900 456 529 80-1/2 40.79 56.81 18.
57 Figure 2a: Series 32 Steam Boilers - Arrangement Of Steam Riser Connections, Draft Hoods And Base Assemblies
6 Figure 2b: Series 32 Water Boilers - Arrangement Of Water Supply Connections, Draft Hoods And Base Assemblies
III Before Installing 1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance with this manual and the requirements of the authority having jurisdiction. • In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the latest edition of the National Fuel Gas Code, ANSI Z223.1.
Boile r Model Ove r All Length Jacke t Ove r All Depth Jacke t 32-475 32-570 32-665 32-760 32-855 32-950 32-1045 32-1140 32-1235 32-1330 32-1425 32-1520 32-1615 32-1710 32-1805 32-1900 32-1995 32-2090 32-2185 32-2280 32-2375 32-2470 32-2565 32-2660 32-2755 32-2850 36 3/4 42 1/4 47 5/8 53 1/8 58 1/2 64 69 3/8 74 7/8 80 1/4 85 3/4 91 1/8 96 5/8 102 107 1/2 112 7/8 118 3/8 123 3/4 129 1/4 134 5/8 140 1/8 145 1/2 151 156 3/8 161 7/8 167 1/4 172 3/4 32 1/4 32 1/4 32 1/4 32 1/4 32 1/4 32 1/4 32 1/4 32 1/4 32
Left Side Right Side Minimum Clearance - Jacket Service Clearance To NonTo Combustible Or NonCombustible Construction Combustible Construction 24" 18" (Controls) 24" 18" (Controls) Clearances Required For Removal Of Tankless Heater T-1 T-2 T-3 27" 32" 42" 27" 32" 42" Front 24" 36" (Cleaning-Burner Removal) -------- -------- -------- Rear 24" 36" (Cleaning) -------- -------- -------- Top 24" -------- -------- -------- --------------------- Table 3: Minimum Clearances to Combusti
V Knockdown Boiler Assembly Instructions A. Prior To Assembly 1) Thoroughly inspect the cast iron heat exchanger sections for any shipping damage, i.e. cracks in the castings, broken lugs or punctures due to mishandling. 2) Do not use a damaged heat exchanger section. Replace it with an undamaged heat exchanger section. 3) Keep the base in the shipping carton until it is time to perform the assembly. This keeps foreign material from contaminating the burners or creating other hazards.
11 Figure 4: Multiple Base Assembly
C. Section Assembly 1) Clean the boiler sections inside and out to remove dirt due to shipping and handling. 2) Clean all nipples and nipple ports with kerosene immediately prior to section assembly. 3) Set the left end section on the base so that the locating lugs on the bottom of the section go inside the front and rear base panels. Left end sections are identified by “LEH” cast on the section. Right end sections are identified by “REH” cast on the section.
Figure 5: Use Of Nipple Gauge Figure 6: Assembly Of Sections 13 15
14) Install the tankless coil/s and/or cover plates using the gaskets and 3/8 x 7/8 bolts and washers provided (see Figure 7). 15) Test assembled block for leaks. Unless local codes have other requirements, use the following procedure: a) Run a hose from the water service to one of the lower tappings. Install a ball or gate valve in one of the tappings on the top of the block and connect the other end of this valve to a drain. Install a gauge in any other convenient tapping.
NOTE Installation of the draft hoods will be easier if one person supports the rear of the hood while another installs the carriage bolts, nuts and washers. 6) Hang a rear tie rod channel bracket on the 4" stud installed in the left end section (Figure 12a). 7) Facing the rear of the boiler, find the square mounting holes underneath the draft hood. Drop a 5/16 x 5" carriage bolt through this hole and through the hole in the rear tie rod channel bracket.
Figure 11: Front Attachment Of Draft Hood Figure 12a: Mounting Rear Tie Rod Channel Bracket Figure 12b: Rear Attachment Of Draft Hood 18 16
D. Jacket Assembly Instructions NOTE Before installing the jacket, make sure to plug any tappings which are not going to be used. Also make sure that no tappings are plugged which will be needed later for piping the boiler. See Sections VIII and IX for piping and trim installation. 1) On the left and right side base panels attach the jacket side panel zee bracket and the jacket top support bracket end angle with #10 x 1/2” sheet metal screws as shown in Figure 13.
18 Figure 14: Exploded View Of Jacket Assembly
VI Air For Combustion and Ventilation Sufficient fresh air must be supplied for combustion, ventilation and flue gas dilution. Provisions for combustion, ventilation and flue gas dilution air for gas utilization equipment vented by natural draft must be made in accordance with local building codes or, in absence of such codes, in accordance with the National Fuel Gas Code, NFPA 54/ANSI Z223.1. Warning An adequate supply of combustion and ventilation air must be provided to assure proper combustion.
Figure 15: Boiler Installed In Confined Space, All Air From Inside • If providing openings into adjacent rooms is undesirable, combustion and ventilation air can be brought into the boiler room from outdoors. See the instructions under “For Buildings of Unusually Tight Construction”. B. For Buildings Of Unusually Tight Construction 1) Provide outdoor air through two permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely exchanging air with the outdoors.
Figure 16: All Air From Outdoors, Ventilated Crawl Space & Attic Figure 17: All Air From Outdoors, Via Ventilated Attic Figure 18: All Air From Outdoors, Using Openings Into Boiler Room 23 21
Figure 19: All Air From Outdoors, Using Horizontal Ducts Into The Boiler Room 24 22
VII Venting Vent installation must be in accordance with local building codes, or the authority having jurisdiction, or the National Fuel Gas Code, NFPA 54/ANSI Z223.1. Typical vent installations are shown in Figures 20 and 21. The vent system shown in Figure 20 uses a common vent for all boiler modules. In Figure 21, each boiler module is equipped with its own vent.
6) Lateral venting should slope upwards towards the chimney not less than one inch in four feet. No portion of vent pipe should run downward or have sags. Vent pipe must be securely supported. 7) The connector rise coming off the boiler should be as tall as possible, while still maintaining the proper clearance from the horizontal vent connector to combustibles and the proper pitch called for in (6) above. 8) Lateral vent pipe should be installed above the bottom of the chimney to prevent blockage.
Figure 20: Typical Series 32 Venting (Common Module Venting) Figure 21: Series 32 Venting (Each Module Individually Vented) 27 25
Removing An Existing Boiler From A Common Chimney In some cases, when an existing boiler is removed from a common chimney, the common venting system may be too large for the remaining appliances. At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
VIII Steam Boiler Piping & Trim Installation CAUTION • INSTALL BOILER SO THAT THE GAS IGNITION SYSTEM COMPONENTS ARE PROTECTED FROM WATER (DRIPPING, SPRAYING, RAIN, ETC.) DURING APPLIANCE OPERATION AND SERVICE (CIRCULATOR REPLACEMENT, ETC.). • OPERATION OF THIS BOILER IN A SYSTEM HAVING SIGNIFICANT AMOUNTS OF DISSOLVED OXYGEN CAN CAUSE SEVERE HEAT EXCHANGER CORROSION DAMAGE. A.
Hydrolevel CG450 – This is a probe type LWCO and is installed in tapping “G”. On the CSD-1 control package, and other boilers with redundant low water cut-offs, the CG450 is the operating low water cut-off and should be used to control a feeder (if used). The CG450 supplied with the Series 32 uses a special probe which does not have a mounting flange. Install this probe in tapping “G”. DO NOT INSTALL WITH TEFLON TAPE.
Figure 22: Steam Boiler Tapping Locations Tapping Uses Chart For Steam Boilers1 Component Description Tapping Location A B Tapping Size (in) 3 3 Standard Equipment N N CSD-1 Package N N Safety Relief Valves (With Inlet Opening Up To & Including 1-1/2" NPT Inlet) C2 1-1/2 Y Y Safety Relief Valves (With Inlets Larger Than 1-1/2" NPT Inlet) Riser (See Figure 27c) - Y Y Pressure Gauge Water Gauge Glass Fittings D E 1/2 1/2 Y Y Y Y M & M #67 Low Water Cut-Off M & M #67M Low Water Cut-Off with
f. g. Boiler Drain Valve - Install with a 3” x ¾” bushing into one of the two return tappings “B”. The drain valve may also be installed in the return piping, but it must be installed in the leg of a tee so that it is directly opposite and as close as possible to the return tapping. The leg of the tee must be at least 1½” pipe size. A bottom blowoff using a valve must also be connected to one of the return tappings (B).
Figure 25: Common Near-Boiler Piping Mistakes Steam Steam Return Condensate Equalizer Boiler Header Riser Pipe Header Return Pipe Pipe Model Size (in) Quantity Size (in) Size (in) Quantity Size (in) Quantity Size (in) 32-380 3 1 3 1 1/2 1 1 1/2 1 2 32-475 3 1 3 1 1/2 1 1 1/2 1 2 32-570 4 2 3 1 1/2 1 1 1/2 1 2 32-665 4 2 3 2 1 2 1 2 1/2 32-760 4 2 3 2 1 2 1 2 1/2 32-855 4 2 3 2 1 2 1 2 1/2 32-950 5 2 3 2 1 2 1 2 1/2 32-1045 5 3 3 2 1 2 1 2 1/2 32-1140 5 3 3 2 1/2 1 2 1 2 1/2 32-1235 5 3 3 2 1/2 1 2 1 2 1/2 3
32 Figure 26: Typical Near-Boiler Piping When Using A Boiler Feed Pump
33 Figure 27a: Recommended Steam Boiler Piping: 1 or 2 Supply Connections, Gravity Return
34 Figure 27b: Recommended Steam Boiler Piping: 3 Supply Connections, Gravity Return
35 Figure 27c: Recommended Steam Boiler Piping: 4, 5 or 6 Supply Connections, Gravity Return
B. Indirect Water Heating Piping (Steam Boilers) The steam version of the Series 32 boiler is equipped with tappings to permit the connection of a Crown Mega-Stor, or other indirect water heater. In this type of system, hot boiler water is drawn from below the water line and passed through the heat exchanger in the indirect water heater. This section describes boiler-side piping only. Refer to the indirect water heater instruction manual for domestic water piping.
IX Water Boiler Piping CAUTION • INSTALL BOILER SO THAT THE GAS IGNITION SYSTEM COMPONENTS ARE PROTECTED FROM WATER (DRIPPING, SPRAYING, RAIN, ETC.) DURING APPLIANCE OPERATION AND SERVICE (CIRCULATOR REPLACEMENT, ETC.). • OPERATION OF THIS BOILER WITH CONTINUOUS RETURN TEMPERATURES BELOW 120°F CAN CAUSE SEVERE HEAT EXCHANGER CORROSION DAMAGE. • OPERATION OF THIS BOILER IN A SYSTEM HAVING SIGNIFICANT AMOUNTS OF DISSOLVED OXYGEN CAN CAUSE SEVERE HEAT EXCHANGER CORROSION DAMAGE.
DANGER • CONFIRM RELIEF VALVE HAS THE CORRECT PRESSURE SETTING AND CAPACITY FOR THE BOILER. • PIPE THE PRESSURE RELIEF VALVE DISCHARGE TO A SAFE LOCATION. • DO NOT INSTALL A VALVE IN THE RELIEF VALVE DISCHARGE LINE. • DO NOT PLUG RELIEF VALVE DISCHARGE. 3) In addition to the boiler trim, the following system components are required: a. Circulator - The best circulator location is usually on the supply piping just downstream of the expansion tank as shown in Figure 30. b.
Figure 29: Water Boiler Tapping Locations Tapping Uses Chart For Water Boilers1 Component Description Tapping Location SupplyPiping A 3 N N Return Piping B 3 N N Pressure Relief Valves C2 1-1/2 Y Y Combination Pressure / Temperature / Altitude Gauge E 1/2 Y Y Hydrolevel #750 Probe Low Water Cut-Off SupplyRiser - N Y Honeywell L4006APressure Limit Control D 1/2 Y Y SupplyRiser - N Y Boiler Drain Valve B 3 Y Y Cover Plate F - Y Y Optional Tankless Heater F - N
40 Figure 30: Typical Water Boiler System Piping
Supply Supply Water Return Return Water Boiler Header Riser Connections Header Connections Model Size (in) Quantity Size (in) Size (in) Quantity Size (in) 32-475 2 1 2 2 1 2 32-570 2 1 2 2 1 2 32-665 2 1/2 1 2 1/2 2 1/2 1 2 1/2 32-760 2 1/2 1 2 1/2 2 1/2 1 2 1/2 32-855 2 1/2 1 2 1/2 2 1/2 1 2 1/2 32-950 3 1 3 3 1 3 32-1045 3 1 3 3 1 3 32-1140 3 1 3 3 1 3 32-1235 3 1 3 3 1 3 32-1330 3 1 3 3 1 3 32-1425 3 1 3 3 1 3 32-1520 3 2 2 1/2 3 2 2 1/2 32-1615 3 2 2 1/2 3 2 2 1/2 32-1710 3 2 2 1/2 3 2 2 1/2 32-1805 3 2
B. TANKLESS HEATER PIPING If the Series 32 water boiler is installed with an optional tankless heater, pipe the heater as shown in Figure 32. The components in this system and their functions are as follows: 1) Mixing Valve (Required) - During the heating season, the water exiting the tankless heater may be 180 degrees or more. The mixing valve blends hot water leaving the tankless heater with cold water so as to maintain the hot water supplied to the fixtures at a fixed temperature.
8) Multiple Tankless Heaters - If two tankless heaters are installed in the boiler, it is recommended that each heater be installed in parallel with its own mixing valve, relief valve, flow restrictor, etc.. This will permit either heater to be removed from service for maintenance while still providing some domestic water to the building.
X Gas Piping 1) Gas piping to the boiler must be sized to deliver an adequate supply of gas for the boiler to fire at the nameplate input with the inlet pressure at the gas valves between the minimum and maximum valves shown on the rating plate. For more information on gas line sizing, consult the Utility or the National Fuel Gas Code. 2) Figure 33 shows the typical gas piping connection(s) to the Series 32 boiler. A sediment trap must be installed upstream of all gas controls.
XI Control System Wiring WARNING All wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code (ANSI/NFPA 70). 1) Provide the boiler with a dedicated branch circuit with a fused disconnect. The minimum rating of this circuit must be 15A. 2) Wire the boiler following the appropriate wiring diagram in Figures 35 or 36. Use 14 gauge wire for all 120 volt boiler wiring.
6) Once the ignition module detects the presence of a pilot flame, voltage is applied across the main valve, opening the valve and establishing main flame. 7) The way in which the ignition module handles failure to establish pilot or the loss of an already established pilot depends upon the exact ignition module supplied with the boiler. For more information on module operation, consult the ignition module instructions supplied with the boiler or the local Crown representative.
Figure 35: Series 32 Standard Boiler Wiring 49 47
Figure 36: Series 32 - CSD-1 Boiler Wiring 50 48
Safety Control Operation Temperature Limit Control (Water Boilers) – The temperature limit control interrupts burner operation when the supply water temperature exceeds the set point. Maximum allowable water temperature in a water boiler is 250F. The L4006A will reset itself when the water temperature drops below the set point less the differential (typically 15F). Manual reset water limit controls, such as the Honeywell L4006E, must be manually reset.
XII Start-up and Checkout NOTE SAFE LIGHTING AND OTHER PERFORMANCE CRITERIA WERE MET WITH THE GAS MANIFOLD AND CONTROL ASSEMBLY PROVIDED ON THE BOILER WHEN THE BOILER UNDERWENT THE TESTS SPECIFIED IN Z21.13. Use the following procedure for initial start-up of the boiler: 1) Make sure that the boiler is filled with water. 2) Check all new gas piping for leaks and purge piping sections that are filled with air. See the National Fuel Gas Code for additional information on testing and purging gas lines.
WARNING FAILURE TO FOLLOW THE FOLLOWING PROCEDURE EXACTLY COULD RESULT IN OVER-FIRING OF THE BOILER AND A CARBON MONOXIDE HAZARD. 13) Check the manifold pressure and adjust if necessary. To do this, use the following procedure: a. Connect a manometer to the inlet pressure tap on the gas valve (see Figures 39 - 41). b. Check the inlet pressure with all gas appliances on and off.
16) (Steam Boilers) - Verify low water cutoff operation while the boiler is running. Slowly open drain valve and drain boiler until the water level drops below low water cutoff line. Water still should be visible in the gauge glass when the low water cutoff shuts down the main burners. The pilot burner and main burners should stop firing. Make sure pressure limit, thermostat or other controls have not shut off the boiler. Upon test completion refill the boiler to the normal water level.
Figure 39: Gas Valve Detail - Honeywell VR8304 Figure 40: Gas Valve Detail - Robertshaw 7000DERHC Figure 41: CSD-1 Gas Train 55 53
LIGHTING INSTRUCTIONS FOR BASE MODULES EQUIPPED WITH HONEYWELL VR8304 SERIES GAS VALVES FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand. If you cannot reach your gas supplier, call the fire department. C.
LIGHTING INSTRUCTIONS FOR BASE MODULES EQUIPPED WITH ROBERTSHAW 7000DERHC SERIES GAS VALVES FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand. If you cannot reach your gas supplier, call the fire department. C.
XIII Service and Maintenance The following routine maintenance should be performed: On a continuous basis: 1) Keep the area around the boiler free and clear from combustible materials, gasoline, and other flammable vapors and liquids. 2) Keep the area around the boiler and boiler room ventilation openings clear of objects which might obstruct the flow of combustion and ventilation air.
12) Place the boiler back in operation using the procedure outlined in “Start-up”. Check the pilot line and any other gas piping disturbed during the inspection process for leaks. Heat Exchanger Cleaning Procedure 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) 13) 14) 15) Turn off electrical power and gas supply to the boiler Disconnect the vent connectors from the boiler. Remove the front, top and rear jacket panels. Remove the burners.
XIV PARTS The following parts may be obtained from any Crown distributor. To find the closest Crown distributor, consult the area Crown representative or the factory at: Crown Boiler Co. Customer Service P.O. Box 14818 Philadelphia PA. 19134 (215) 535-8900 www.crownboiler.com For boilers installed at elevations above 2000 ft, consult the local Crown representative or the factory for the correct main burner orifice.
59 1 1 32-2850 1 32-1995 1 1 32-1900 32-2755 1 32-1805 32-2660 1 32-1710 1 1 32-1615 32-2565 1 32-1520 1 1 32-1425 32-2470 1 32-1330 1 1 32-1235 1 1 32-1140 32-2375 1 32-1045 32-2280 1 32-950 1 1 32-855 1 1 32-760 32-2090 1 32-665 32-2185 1 1 32-475 32-570 BOILER MODEL 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 25 24 2
TANKLESS COILS PARTS MODEL PART # T-1 310020 T-2 310021 T-3 310022 BASE CARTON DESCRIPTION PART # 285 BASE ASSEMBLY (STD) 310114 380 BASE ASSEMBLY (STD) 310115 475 BASE ASSEMBLY (STD) 310116 285 BASE ASSEMBLY (CSD-1) 3101145 380 BASE ASSEMBLY (CSD-1) 3101155 475 BASE ASSEMBLY (CSD-1) 3101165 REAR TIE ROD CHANNEL BRACKET 310311 285 QUANTITY 380 475 1 1 1 1 1 1 1 1 1 5/8 X 4 STUD 900309 1 1 1 5/8 USS WASHER 900312 2 2 2 5/8 NUT 900311 2 2 2 JACKET REAR PANEL SUPPOR
SECTION JOINER CARTON DESCRIPTION QUANTITY PART # "A" "B" "C" "D" "E" 7" PUSHNIPPLE 310005 5 6 7 8 9 3" PUSHNIPPLE 310006 5 6 7 8 9 5/8 X 9 3/4 TIE ROD 900310 15 18 21 24 27 5/8 HEX NUT 900311 30 36 42 48 54 5/8 FLAT WASHER 900312 30 36 42 48 54 LOCTITE # 592, 50 ml TUBE 900350 2 3 3 LOCTITE # 592, 250 ml TUBE 900355 1 1 "SECTION SEAL", 1 QUART CAN 900360 2 2 2 2 2 WOOD WEDGE 970030 2 2 2 2 2 BASE SIDE CARTON DESCRIPTION PART # QTY.
BASE PARTS KEY PART # DESCRIPTION QTY PER BASE MODULE 285 380 475 1 BASE FRONT PANEL (285) 310604 1 1 BASE FRONT PANEL (380) 310605 1 BASE FRONT PANEL (475) 310606 2a BASE FRONT LEG (RH) 310110 1 1 1 2b BASE FRONT LEG (LH) 310111 1 1 1 3 INSULATION BASE FRONT (285) 312614 1 3 INSULATION BASE FRONT (380) 312615 3 INSULATION BASE FRONT (475) 312616 4 BASE REAR PANEL (285) 310664 4 BASE REAR PANEL (380) 310665 4 BASE REAR PANEL (475) 310666 5 RIGHT SIDE PANEL 31
63 Figure 42: Exploded View - Base Parts
BASE PARTS (CONTD.) KEY DESCRIPTION PART # QUANTITY 285 380 475 20 MANIFOLD ASSY, COMPLETE (285) 310154 1 20 MANIFOLD ASSY, COMPLETE (380) 310155 20 MANIFOLD ASSY, COMPLETE (475) 310156 21 1/4-20 X 1/2 SELF TAPPING SCREW 900100 4 4 4 22 MAIN BURNER LESS PILOT BRKT 150321 7 10 13 1 1 23 MAIN BURNER WITH PILOT BRKT.
65 Figure 43: Exploded View - Gas Manifold / Burners / Pilot Assembly
WATER TRIM CARTON DESCRIPTION PART # QTY L4006A2015 35-3510 1 L4006E1109 MAN.
67 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 32-1045W 32-1140W 32-1235W 32-1330W 32-1425W 32-1520W 32-1615W 32-1710W 32-1805W 32-1900W 32-1995W 32-2090W 32-2185W 32-2280W 32-2375W 32-2470W 32-2565W 32-2660W 32-2755W 32-2850W 1 1 32-950W 1 1 32-855W 1 1 32-760W 1 1 32-665W 1 1 32-570W 1 1 32-475W 1 1 BOILER MODEL 1 ETL RATING PLATE 98-111 1 INSTALLATION MANUAL 980888 1 USER'S MANUAL 980425 1 NIPPLE GAUGE 980920 1 RESBOND 907GF-6CP, 11 oz
68 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 32-1425S 32-1520S 32-1615S 32-1710S 32-1805S 32-1900S 32-1995S 32-2090S 32-2185S 32-2280S 32-2375S 32-2470S 32-2565S 32-2660S 32-2755S 32-2850S 1 1 32-1330S 1 1 32-1235S 1 1 32-1140S 1 1 32-1045S 1 1 32-950S 1 1 32-855S 1 1 32-760S 1 1 32-665S 1 1 32-570S 1 1 32-475S 1 1 BOILER MODEL 1 ETL RATING PLATE 98-111 1 INSTALLATION MANUAL 980888 1 USER'S MANUAL 980425 1 NIPPLE GAUGE 980920 1 RESBOND 907GF
Manufacturer of Hydronic Heating Products P.O. Box 14818 3633 I. Street Philadelphia, PA 19134 Tel: (215) 535-8900 • Fax: (215) 535-9736 • www.crownboiler.com 71 PN 980888 Rev.