Data Sheet

3 | CONTROL.CROUZET.COM 11/2018 | Plug-In Timer
PU2R10MV1 PA2R10MV1 PC2R10MV1 PL2R10MV1
Storage temperature (IEC 60068-2) -40 °C to +70 °C
Humidity (IEC 60068-2-30) 93 % without condensation
Vibration resistance (IEC 60068-2-6) ±0.15mm from 10 Hz…60 Hz 2 g from 60 Hz..150 Hz
Shock resistance (IEC60068-2-27) 10 gn - 11 ms; 3 X 6 axis (Output non-energized) 5 gn - 11 ms; 3 X 6 axis (Output energized)
Drop to concrete oor (IEC 60068-2-32) High: 0.75 m
Weight 90 g
110 g with packaging
Standards
CEE Directive: 2014/30/EU
2014/35/EU
EMC
Low voltage
Approvals / Marking CE
cULus Listed Industrial Control Equipment
Security standard (IEC 60664-1) Insulation coordination for equipment within low-voltage systems
Conformity with environmental directives:
2015/863/UE
1907/2006
2012/19/UE
RoHS
Reach
WEEE
Product standard
(IEC 61812-1 / UL 60947-4-1)
Specied time relays for industrial use
Industrial Control Equipment (NRNT- Industrial Control Switches)
Refer to UL840 Insulation Coordination for Electrical Equipment
Electromagnetic compatibility:
IEC 61000-6-2
IEC 61000-6-3
IEC 61000-6-4
Generic standards
Immunity for industrial environment
Emission residential environment
Emission industrial environment
Immunity to electrostatic discharges
(IEC61000-4-2)
Level III Air ±8 KV / Contact ±6 KV
Immunity to radiated, radio-frequency,
electromagnetic eld (IEC61000-4-3)
Level III
10 V/m (80 MHz to 1 GHz) 80 % AM (1 kHz)
3 V/m (1.4 to 2 GHz) 80 % AM (1 KHz)
1 V/m (2 to 2.7 GHz) 80 % AM (1 KHz)
Immunity to rapid transient bursts (IEC
61000-4-4)
direct ±4 kV 5/50 Tr/Th ns 5 KKz & 100 KHz
Capacitive coupling clamp ± 2 KV 5/50 Tr/Th ns 5 KHz & 100 KHz
Immunity to shock waves on power supply
(IEC 61000-4-5)
Level III: line-to-earth ±2 kV / line-to-line ±1 kV
Immunity to radiofrequency in common
mode (IEC 61000-4-6)
Level III: 10 Vrms (0.15 to 80 MHz) 80 % AM (1 kHz)
Immunity to voltage dips and breaks
(IEC 61000-4-11)
0 % residual voltage during 1 cycle (Crit. B)
40 % residual voltage / 10 cycles 50 Hz / 12 cycles 60 Hz (Crit. C)
70 % residual voltage / 25 cycles 50 Hz / 30 cycles 60 Hz (Crit. C)
Short interruptions:
0 % residual voltage / 250 cycles 50 Hz / 300 cycles 60 Hz (Crit. C)
AC/DC main port emissions
(IEC 61000-6-3 IEC 61000-6-4)
CISPR 16-2-1 (7.4.1), CISPR 16-1-2 (4.3)
0.15 MHz – 0.5 MHz, 66 dB(μV) – 56 dB(μV) quasi-peak, 56 dB(μV) – 46 dB(μV) average
0.5 MHz – 5 MHz, 56 dB(μV) quasi-peak, 46 dB(μV) average
5 MHz – 30 MHz, 60 dB(μV) quasi-peak, 50 dB(μV) average
CISPR 14-1
0.15 MHz – 30 MHz
CISPR 16-2-1 (7.4.1), CISPR 16-1-2 (4.3)
0.15 MHz – 0.5 MHz, 79 dB(μV) quasi-peak, 66 dB(μV) average
0.5 MHz – 30 MHz, 73 dB(μV) quasi-peak, 60 dB(μV) average
Radiated emissions
(IEC 61000-6-3 IEC 61000-6-4)
CISPR 16-2-3
30 MHz – 230 MHz, 30 dB(μV/m) Quasi-peak at 10 m
230 MHz – 1 000 MHz, 37 dB(μV/m) Quasi-peak at 10 m
Or: 30 MHz – 230 MHz, 40 dB(μV/m) Quasi-peak at 3 m in a semi-anechoic chamber
230 MHz – 1 000 MHz, 47 dB(μV/m) Quasi-peak at 3 m in a semi-anechoic chamber