3-phase network control relays monitor the sequence of phases L1, L2, L3 and failure of one or more phases.
LEDs are used for signalling.
Operating principle
MWS-MWS2 : Phase controller
The relay monitors its own supply voltage.
The relay controls :
- correct sequencing of the three phases,
- total failure of one of the three phases.
When the phase sequence and voltages are correct (> 183 VAC), the output relay (s) are closed and the yellow LED is lit.
In the event of a phase sequence or total phase failure fault (detected when one of the voltages drops below 100 V), the relay opens instantly and its LED is extinguished.
When the unit is powered up with a measured fault, the relay stays open.
Storage temperature IEC/EN 60068
-2
-
40→+70°C
Humidity IEC/EN 60068
-2-30
2 x 24 hr cycle 95 % RH max. without condensation 55 °C
Vibrations according to IEC/EN60068
-2-6
10→150Hz,A=0.035mm
Shocks IEC/EN 60068
-2-6
5 g
Standards
Standards
IECI/EN 50178, IEC/EN 61000
-6-
2, IEC/EN 61000
-6-3
Certifications
CE, UL, CSA, GL
Conformity with environmental directives
RoHS, WEEE
Supply
Supply voltage Un
3x208→3x480VAC
Operating range
183→528VAC
Inputs and measuring circuit
Measurement ranges
183→528VAC
General characteristics
Weight
80 g
Comments
Description
Code
Removable sealable cover for 17.5 mm casing
84800000