The under or overvoltage threshold value is set by a graduated potentiometer by reading the Un scale to be monitored directly.
The hysteresis is set by a graduated potentiometer from 5 to 20% of the preset threshold. The hysteresis value cannot be higher than the extremes of the measurement range.
In overvoltage mode, if the controlled voltage exceeds the preset threshold for longer than the time set on the front face (0.1 to 10 s), the output relay opens and LED R is extinguished. During the
time delay, this LED flashes.
Once the voltage falls below the threshold value minus the hysteresis, the relay closes instantaneously.
In undervoltage mode, if the controlled voltage falls below the preset threshold for longer than the time set on the front face (0.1 to 10 s), the output relay opens and LED R is extinguished. During
the time delay, this LED flashes.
Once the voltage rises above the threshold value plus the hysteresis, the relay closes instantaneously.
-
40→70°C
2 x 24 hr cycle 95% RH max. without condensation 55°C
10→150Hz,A=0.035mm
5 g
Standards
CE (LVD) 73/23/EEC
-
EMC 89/336/EEC
NF EN 60255
-
6 / IEC 60255
-
6 / UL 508 / CSA C22.2 N°14
Immunity EN 61000
-6-
2/IEC 61000
-6-2
Emission EN 61000
-6-
4/EN 61000
-6-3
IEC 61000
-6-
4/IEC 61000
-6-3
Emission EN 55022 class B
UL, CSA, GL
RoHS, WEEE
Supply
110→240VAC/DC
3 VA in AC/1 W in DC
50→270VAC/DC
65→260VAC/DC
Inputs and measuring circuit
5→20%ofthreshold(MUS)
3% (fixed) of threshold (MUSF)
General characteristics
80 g
Description
Code
Removable sealable cover for 17.5 mm casing
84800000
Dimension Diagram : MUS
-
MUSF
: MUS
-
Under/overvoltage
- without latching
N
o
Legend
1
Threshold
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
13/03/2012 www.crouzet.com