Datasheet
The under or overvoltage threshold value is set by a graduated potentiometer by reading the Un scale to be monitored directly.
The hysteresis is set by a graduated potentiometer from 5 to 20% of the preset threshold. The hysteresis value cannot be higher than the extremes of the measurement range.
In overvoltage mode, if the controlled voltage exceeds the preset threshold for longer than the time set on the front face (0.1 to 10 s), the output relay opens and LED R is extinguished. During the
time delay, this LED flashes.
Once the voltage falls below the threshold value minus the hysteresis, the relay closes instantaneously.
In undervoltage mode, if the controlled voltage falls below the preset threshold for longer than the time set on the front face (0.1 to 10 s), the output relay opens and LED R is extinguished. During
the time delay, this LED flashes.
Once the voltage rises above the threshold value plus the hysteresis, the relay closes instantaneously.
Storage temperature IEC/EN 60068
-2
-
40→70°C
Humidity IEC/EN 60068
-2-30
2 x 24 hr cycle 95% RH max. without condensation 55°C
Vibrations according to IEC/EN60068
-2-6
10→150Hz,A=0.035mm
Shocks IEC/EN 60068
-2-6
5 g
Standards
Marking
CE (LVD) 73/23/EEC
-
EMC 89/336/EEC
Product standard
NF EN 60255
-
6 / IEC 60255
-
6 / UL 508 / CSA C22.2 N°14
Electromagnetic compatibility
Immunity EN 61000
-6-
2/IEC 61000
-6-2
Emission EN 61000
-6-
4/EN 61000
-6-3
IEC 61000
-6-
4/IEC 61000
-6-3
Emission EN 55022 class B
Certifications
UL, CSA, GL
Conformity with environmental directives
RoHS, WEEE
Supply
Nominal voltage (V)
110→240VAC/DC
Power consumption at Un
3 VA in AC/1 W in DC
Operating range
50→270VAC/DC
Range of adjustment
65→260VAC/DC
Inputs and measuring circuit
Hysteresis
5→20%ofthreshold(MUS)
3% (fixed) of threshold (MUSF)
General characteristics
Weight
80 g
Description
Code
Removable sealable cover for 17.5 mm casing
84800000
Dimension Diagram : MUS
-
MUSF
: MUS
-
Under/overvoltage
- without latching
N
o
Legend
1
Threshold
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
13/03/2012 www.crouzet.com