Datasheet
Program memory
Flash EEPROM
Removable memory
EEPROM
Data memory
368 bits/200 words
Back-up time in the event of power failure
Program and settings in the controller: 10 years
Program and settings in the plug
-in memory: 10 years
Data memory: 10 years
Cycle time
Ladder: typically 20 ms
FBD:6→90ms
Response time
Input acquisition time + 1 to 2 cycle times
Clock data retention
10 years (lithium battery) at 25 °C
Clock drift
Drift < 12 min/year (at 25 °C)
6 s/month (at 25 °C with user-definable correction of drift)
Timer block accuracy
1%
±
2 cycle times
Start up time on power up
< 1,2 s
Characteristics of products with AC power supplied
Supply
Nominal voltage
24 V AC
100→240VAC
Operating limits
-15% / +20%
or20.4VAC→28.8VAC
-15% / +10%
or85VAC→264VAC
Supply frequency range
50/60 Hz (+4% / -6%)
or47→53Hz/57→63Hz
50/60 Hz (+ 4% / -6%)or47→53Hz/57→63Hz
Immunity from micro power cuts
10 ms (repetition 20 times)
10 ms (repetition 20 times)
Max. absorbed power
CB12
-
CD12
-
XD10
-XB10: 4 VA
CB20
-CD20: 6 VA
XD10
-XB10 with extension -
XD26
-XB26: 7.5 VA
XD26
-XB26 with extension: 10 VA
CB12
-
CD12
-
XD10
-XB10: 7 VA
CB20
-CD20: 11 VA
XD10
-XB10 with extension -
XD26
-XB26: 12 VA
XD26
-XB26 with extension: 17 VA
Isolation voltage
1780 V AC
1780 V AC
Inputs
Input voltage
24 V AC (-15% / +20%)
100→240VAC(-15% / +10%)
Input current
4.4 mA @ 20.4 V AC
5.2 mA @ 24.0 V AC
6.3 mA @ 28.8 V AC
0.24 mA @ 85 V AC
0.75 mA @ 264 V AC
Input impedance
4.6 k
Ω
350 k
Ω
Logic 1 voltage threshold
≥14VAC
≥79VAC
Making current at logic state 1
> 2 mA
> 0.17 mA
Logic 0 voltage threshold
≤5VAC
≤20VAC(≤28VAC:XE10,XR06,XR10,XR14)
Release current at logic state 0
< 0.5 mA
< 0.5 mA
Response time with LADDER programming
50 ms
State0→1(50/60Hz)
50 ms
State0→1(50/60Hz)
Response time with function blocks programming
Configurable in increments of 10 ms
50 ms min. up to 255 ms
State0→1(50/60Hz)
Configurable in increments of 10 ms
50 ms min. up to 255 ms
State0→1(50/60Hz)
Maximum counting frequency
In accordance with cycle time (Tc) and input response time (Tr) :
1/ ( (2 x Tc) + Tr)
In accordance with cycle time (Tc) and input response time (Tr) :
1/ ( (2 x Tc) + Tr)
Sensor type
Contact or 3-
wire PNP
Contact or 3-
wire PNP
Input type
Resistive
Resistive
Isolation between power supply and inputs
None
None
Isolation between inputs
None
None
Protection against polarity inversions
Yes
Yes
Status indicator
On LCD screen for CD and XD
On LCD screen for CD and XD
Characteristics of relay outputs common to the entire range
Max. breaking voltage
5→30VDC
24→250VAC
Breaking current
CB
-
CD
-
XD10
-
XB10
-
XR06
-
XR10: 8 A
XD26
-XB26: 8 x 8 A relays, 2 x 5 A relays
XE10: 4 x 5 A relays
XR14: 4 x 8 A relays, 2 x 5 A relays
Electrical durability for 500 000 operating cycles
Utilization category DC
-12: 24 V, 1.5 A
Utilization category DC
-13: 24 V (L/R = 10 ms), 0.6 A
Utilization category AC
-12: 230 V, 1.5 A
Utilization category AC
-15: 230 V, 0.9 A
Max. Output Common Current
12 A for O8, O9, OA
Minimum switching capacity
10 mA (at minimum voltage of 12 V)
Minimum load
12 V, 10 mA
Maximum rate
Off load: 10 Hz
At operating current: 0.1 Hz
Mechanical life
10,000,000 (operations)
Voltage for withstanding shocks
In accordance with IEC/EN 60947
-
1 and IEC/EN 60664
-1: 4 kV
Response time
Make 10 ms
Release 5 ms
Built
-in protections
Against short-circuits: None
Against overvoltages and overloads: None
Status indicator
On LCD screen for CD and XD
Characteristics of product with DC power supplied
Supply
Nominal voltage
12 V DC
24 V DC
Operating limits
-13% / +20%
or10.4VDC→14.4VDC(includingripple)
-20% / +25%
or19.2VDC→30VDC(includingripple)
Immunity from micro power cuts
≤1ms(repetition20times)
≤1ms(repetition20times)
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
05/09/2011 www.crouzet.com