Datasheet

The under and overcurrent values are set by two independent potentiometers graduated from 1 to 10 A.
In case of a control error (low threshold higher than high threshold), the output relay opens and all the
LEDs flash to signal the error.
If a current fault occurs (under or overcurrent) the relay opens if the fault persists
beyond the preset threshold delay. When the current returns to a correct value, the output relay remains open. It can only be closed by a reset: either by de-energisation or by closing on external
contact Y2 (in single control mode)
An inhibit delay (Ti) on energisation allows current peaks due to start-up of the motor to be disregarded.
N
o
Legend
1
Undercurrent
2
Hysteresis
3
Relay
4
Fault monitoring inhibit time on pump start
-
up (Ti)
5
Delay timing in case of fault (Tt)
: 3 ph < 10 A
N
o
Legend
1
100 mA fast-blow fuse or cut-out
: 1 ph AC 230 V < 10 A
N
o
Legend
1
100 mA fast-blow fuse or cut-out
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
13/03/2012 www.crouzet.com