Datasheet

The pump controller can operate on a single phase or 3-phase network. It provides 3 functions in one unit:
Checking current,
Checking phase presence (in 3-phase mode),
Checking phase sequence (in 3-phase mode).
It has two operating modes whose purposes is to control a pump based on two external signal inputs (Y1 Y2).
These two signals are controlled by volt-free contacts.
Faults are signalled via LEDs, distinguishing the origin of the fault.
Selecting the operating mode
A rotary switch on the front is used to select:
-
single control mode,
-
dual control mode,
-
single
-phase or 3-phase network.
The position of this selector switch is only taken into account when the unit is powered up.
If the switch position changes while the unit is operating, all the LEDs flash but the product continues to work normally with the mode selected on energisation prior to the change of position.
The LEDs return to their normal state if the switch is reset to its initial position defined before the last energisation.
Incandescent wire test according to IEC 60695-2-
11 & NF EN 60695
-2-11
Terminal block: IP 20
Casing: IP 30
100 g
Rigid: 1 x 4
2
- 2 x 2.5
2
mm
2
1 x 11 AWG - 2 x 14 AWG
Flexible with ferrules: 1 x 2.5
2
- 2 x 1.5
2
mm
2
1 x 14 AWG - 2 x 16 AWG
0,6→1Nm/5,3→8,8Lbf.In
-
20→+50°C
-
40→+70°C
2 x 24 hr cycle 95% RH max. without condensation 55°C
10→150Hz,A=0.035mm
5 g
Standards
CE (LVD) 73/23/EEC
-
EMC 89/336/EEC
NF EN 60255
-
6 / IEC 60255
-
6 / UL 508 / CSA C22.2 N°14
Immunity EN 61000
-6-
2/IEC 61000
-6-2
Emission EN 61000
-6-
4/EN 61000
-6-3
IEC 61000
-6-
4/IEC 61000
-6-3
Emission EN 55022 class B
UL, CSA, GL
RoHS, WEEE
Comments
* 3
-phase mains with earth
Description
Code
Removable sealable cover for 35 mm casing
84800001
Dimension Diagram : HPC