Data Sheet

I Timers I 03 I www.crouzet-control.com
General characteristics
Immunity to radiated, radio-frequency, electromagnetic field acc.
IEC/EN 61000-4-3
Level III
10 V/m (80 M Hz to 1 G Hz) 80 % AM (1 k Hz)
3 V/m (1,4 →2 G Hz) 80 % AM (1K Hz)
1V/m (2 →2.7 G Hz) 80 % AM (1K Hz)
Immunity to rapid transient bursts acc. to IEC/EN 61000-4-4 Level III direct ± 2 kV (power supply) / capacitive coupling clamp
± 1 KV (command input and outputs)
Immunity to shock waves on power supply acc. to IEC/EN 61000-4-5 Level III
line-to-earth ± 2 kV / line-to-line ± 1kV
Immunity to radio frequency in common mode acc. to
IEC/EN 61000-4-6
Level III
10 Vrms (0,15 →80 M Hz) 80 % AM (1 k Hz)
Immunity to voltage dips and breaks acc. to IEC/EN 61000-4-11 Industrial Class II:
0 % residual voltage during 1cycle a.c. power ports
70 % residual voltage during 25/30 cycles a.c. power ports
0 % residual voltage, 250/300 cycles a.c. power ports
Residential:
0 % residual voltage during 10 cycle a.c.power ports
40 % residual voltage during 10 cycles a.c. power ports
70 % residual voltage during 10 cycles a.c. power ports
0 % residual voltage, 250/300 cycles a.c. power ports
Mains-borne and radiated emissions acc. to EN 55022 (CISPR22),
EN55011 (CISPR11)
EN 55022 / CISPR22 Class B (IT equipment)
EN 55011 / CISPR11 Class B, Group 1 (Medical equipment)
Dimensions
Curves
Function L
Asymmetrical timing, off start
R1/R2
Toff Ton
U
Y1
Function Li
Asymmetrical timing, pulse start
R1/R2
Ton Toff
U
Y1
Connections
1 changeover relay output
A1 = Y1 for function L
U
A1
R
15
A2
1816
Y1
+
A1 Y1