Data Sheet

Multi-voltage 12 →240 V AC/DC
LED status indicator
Possibility of external load connection in parallel to the
control input
3-wire PNP sensor compatible
Specifications
Functions Delay Output Nominal rating Connections Supply voltage Code
L - Li 0,1 s →10 days 2 changeover relays 8 A Screw terminals 12 →240 V ∿/⎓ BL2R08MV1
Output relay
Contact arrangement
2 CO (SPDT) (Changeover -Single Pole Double Throw-)
R1: Follow timing function
R2: Follow timing function
Maximum switching voltage 250 VAC/ 8 A resistive / 250 VDC / 0.3 A resistive
Switching current rate (resistive) NO / NC : 8A 250 V AC / 8 A 30 VDC @ 25°C
NO / NC : 5A 250 V AC / 5 A 30 VDC @ 60°C
Minimum switching contact 10 mA / 5 VDC
Maximum switching power (resistive) 2000 VA / 80 W @ 25°C
Electrical life 10
5
cycles min at 250 VAC/ 8 A resistive
Maximum rate (at max switching power) 360 cycles /hour
Mechanical life 10 x 10
6
cycles
Rated impulse voltage 5 kV (1.2/50µs)
Dielectric strength between coil / contacts IEC 60664-1: 5 kV /1 min / 1 mA / 50 Hz
Dielectric strength between open contacts 2,5 kV /1 min / 1 mA / 50 Hz
Timing
Timing ranges (7 ranges) 0.5→10s, 0.05→1min, 0.5→10min, 0.05→1h,
0.5→10h, 0.05→1day, 0.5→10days
Minimum pulse duration typically (relay version) IEC 1812-1: 30 ms / 100 ms with load
Maximum reset time by de-energisation typically (relay version) IEC 1812-1: 120 ms
Repeatability
IEC 1812-1: ≤ ± 0,5 %
Repetition accuracy with constant parameters IEC 1812-1: ≤ ± 10 %
Drift Temperature ≤ ± 0.05 % / °C
Voltage-dependent drift ≤ ± 0.2 % / V