Data Sheet

3 07/2021 | Logic Controller CROUZET.COM
Millenium Slim
CB8R (AC)
Millenium Slim
CB8R (DC)
Millenium Slim
CB8S (DC)
Processing Characteristics
Part Number 88983903 88983901 88983902
HMI / MMI ▪ 1 green Led for Power/Status
▪ 1 blue Led for Bluetooth
▪ Virtual display & keypad with Crouzet Virtual Display or Crouzet Soft
Programming Software Crouzet Soft
Programming method FBD (Function Block Diagram), including SFC (Sequential Function Chart) (Grafcet)
Program size ▪ Function blocks: typically 350 blocks (1024 max.)
▪ Macro blocks: 127 max. (255 blocks per macro)
Program memory Flash
Data memory 2 k octets
Back-up time (in the event of power failure) ▪ Program and settings in the controller: 10 years
▪ Data memory: 10 years
Data back-up Data backup in the ash memory is guaranteed if the product is powered on more than 10 seconds
Cycle time From 2 ms* to 90 ms, default value: 10 ms
*: Depending on program memory
Clock data retention 10 years (lithium battery) at 25 °C (77 °F)
Clock drift Drift < 12 min/year (at 25 °C (77 °F))
6 s / month (at 25 °C (77 °F) with user-denable correction of drift).
Timer block accuracy 0.5 % ± 2 cycle time
Startup time on power up < 3 s
Self-test ▪ Test rmware integrity (checksum memory)
▪ Stability of the internal power supply
▪ Check the conformity of the device conguration with the conguration in the application program.
Power Supply
Part Number 88983903 88983901 88983902
Nominal supply voltage 110 Va → 240 Va 24 Vc
Voltage supply tolerance -15% / +10% -15% / +20%
Operating limits 93.5 → 264 Va
* Accepts temporary
overvoltage occurring on the
power network
20.4 → 28.8 Vc
* Accepts temporary overvoltage occurring on the power network
AC supply voltage frequency 50/60Hz (-6% / +5%) so 47Hz
→ 53Hz / 57 → 63Hz
N/A
Immunity to power micro cuts ≤ 10 ms (repetition 20 times) ≤ 1 ms (repetition 20 times)
Max. absorbed power ▪ 6.9 VA @ 240 Va
▪ 6 VA @ 240 Va I/Os = 0
▪ 1.2 W @ 24 Vc
▪ 1.56 W @ 28.8 Vc,
▪ 0.5 W @ 24 Vc I/Os = 0
▪ 0.75 W @ 24 Vc
▪ 0.8 W @ 28.8 Vc,
▪ 0.5 W @ 24 Vc I/Os = 0
Protection against polarity inversions Not applicable Yes
Power monitoring Yes, but no value available
through the application "FB
Status"
Yes, and value available through the application “FB Status”,
1/10V, 5% of full scale