Data Sheet

I
WWW.CROUZET-AUTOMATION.COM I 06 I em4
Truth table of the default Command Output Fault
Normal condition 0 0 No
1 1 No
Overheating 0 0 No
1 0 Yes
Underpowered 0 0 X
1 0 X
Short circuit (current limit) 0 0 No
1 0 Yes
Output used as PWM output
PWM frequency 14.11 Hz ; 56.45 Hz ; 112.90 Hz ; 225.80 Hz ; 451.59 Hz ; 1758.24 Hz
PWM cyclic ratio
0 100 % 100 steps
PWM Max. error
y 2 % (from 10 % 90 %)
Status indicator On LCD screen
Cable length y 10 m with shielded twisted cable
Distance between the power source and the static outputs y 30 m
6 A relay output - 2 outputs from O3 to O4
Breaking voltage 250 VAC max
Breaking current 6 A ; Derating: UL: u 45°C (113°F): 4A max
Maximum breaking current in the common IEC @ 25°C (77°F): 12 A
IEC @ 60°C (140°F) or UL: 10 A
Mechanical life 5 000 000 operations (cycles)
Electrical durability for 50 000 operating cycles 24 VDC tau = 0 ms: 6 A, tau = 7 ms: 3 A, tau = 15 ms: 1.8 A
Usage category DC-12: 24 V, 6 A
Usage category DC-14: 24 V, 1.8 A
250 VAC cos phi = 1: 6 A, cos phi = 0.7: 5 A, cos phi = 0.4: 2.5 A
Usage category AC-12: 250 V, 6 A
Usage category AC-13: 250 V, 5 A
Usage category AC-15: 250 V, 2 A
Minimum switching capacity 100 mA (at minimum voltage of 12V)
Maximum operating rate Off load: 10 Hz
At operating current: 0.1 Hz
Voltage for withstanding shocks In accordance with IEC/EN 60947-1 and IEC/EN 60664-1: 4 kV
Response time Make = 1 cycle time + 8 ms typical
Release = 1 cycle time + 4 ms typical
Built-in protections Against short-circuits: None
Against over voltages and overload: None
Status indicator On LCD screen
Cable length y 30 m
8 A relay output - 6 outputs from O5 to OA
Breaking voltage 250 VAC max
Breaking current 8 A ; Derating: CEI u 55°C (131°F) or UL: u 45°C (113°F): 6A max
Maximum breaking current in the common IEC @ 25°C (77°F): C3, C6: 8 A ; C4, C5: 16 A
IEC @ 60°C (140°F) or UL: C3, C6: 8 A ; C4, C5: 10 A
Mechanical life 20 000 000 operations (cycles)