Data Sheet
I
WWW.CROUZET-AUTOMATION.COM  I 02  I em4
Frequency range UMTS 850 band V (Downlink) 869 - 894 MHz
Frequency range UMTS 900 band VIII (Uplink) 880 - 915 MHz
Frequency range UMTS 900 band VIII (Downlink) 925 - 960 MHz
Frequency range UMTS 1700 band IV (Uplink) 1710 - 1755 MHz
Frequency range UMTS 1700 band IV (Downlink) 2110 - 2155 MHz
Frequency range UMTS 1900 band II (Uplink) 1850 - 1910 MHz
Frequency range UMTS 1900 band II (Downlink) 1930 - 1990 MHz
Frequency range UMTS 2100 band I (Uplink) 1920 - 1980 MHz
Frequency range UMTS 2100 band I (Downlink) 2110 - 2170 MHz
SIM card Not included
Antenna: impedance 50 Ω
Antenna: input power > 2 W
Antenna: connector RP SMA: SMA female reverse polarity
Antenna: V.S.W.R < 2:1 recommended 
< 3:1 acceptable
Antenna: return loss
S11 < - 10 dB recommended
S11 < - 6 dB acceptable
General characteristics
Products certication  CE, cULus Listed
Conformity with the low voltage directive 
(in accordance with BT 2006/95/EC)
IEC/EN 61131-2 (Open equipment)
Conformity with the EMC directive 
(in accordance with 2004/108/EC)
IEC/EN 61000-6-1 (Residential, commercial and light-industrial environments) 
IEC/EN 61000-6-2 (Industrial) 
IEC/EN 61000-6-3 (Residential, commercial and light-industrial environments) 
IEC/EN 61000-6-4 (Industrial)
Earthing None
Overvoltage category 3 in accordance with IEC/EN 60664-1
Pollution Degree: 2 in accordance with IEC/EN 61131-2
Maximum utilization altitude Operation: 2000 m 
Transport: 3000 m
Mechanical resistance Immunity to vibrations IEC/EN 60068-2-6, Fc test 
Immunity to shock IEC/EN 60068-2-27, Ea test
Resistance to electrostatic discharge Immunity to ESD IEC/EN 61000-4-2, level 3
Resistance to HF interference 
(Immunity)
Immunity to radiated electrostatic elds IEC/EN 61000-4-3, level 3 
Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3 
Immunity to shock waves IEC/EN 61000-4-5 
Radio frequency in common mode IEC/EN 61000-4-6, level 3
Conducted and radiated emissions 
(in accordance with EN 55022/11 group 1)
Class B
Operation temperature
-20°C (-4°F)  +60°C (140°F) (+40°C (104°F) in a non-ventilated enclosure)
Storage temperature
-40°C (-40°F)  +80°C (176°F)
Relative humidity 95% max. (no condensation or dripping water)
Screw terminals connection capacity Flexible wire with ferrule: 1 conductor: 0.2 to 2.5 mm² (AWG 24-14) 
Flexible wire with ferrule: 2 conductors: 0.2 to 0.75 mm² (AWG 24-18) 
Rigid wire: 1 conductor: 0.2 to 2.5 mm² (AWG 24-14) 
Rigid wire: 2 conductors: 0.2 to 0.75 mm² (AWG 24-18) 
Tightening torque: 0.5 N.m (4.5 lb-in) (tighten using screwdriver diam. 3.5 mm) 
Stripping length: 6 mm
Processing characteristics
LCD display Display with 4 lines of 18 characters
Programming method FBD (Function Block Diagram), including SFC (Sequential Function Chart, Grafcet)
Program size Function blocks: typically 1000 blocks 
Macro blocks: 64 max. (256 blocks per macro)
Program memory Flash
Removable memory N.A
Data memory 2 k octets
Backup time 
(in the event of power failure)
Program and settings in the controller: 10 years 
Data memory: 10 years
Data backup Data backup in the ash memory is guaranteed if the product is powered on more 
than 10 seconds